05.06.15 ,
Quite often homeowners, builders and installers have a question about organization of grounding, which they solve in completely different ways. The methods based on the regulations that impose a number of requirements to the configurations and materials of ground electrodes are correct. For example, GOST R 50571.5.54-2013 national standard, which came into effect on 1 January 2015, clearly identifies the materials and dimensions of ground electrodes, see below.
Table 54.1 - Minimum dimensions of grounding electrodes laid in the ground made of the most common materials from the point of view of corrosion and mechanical resistance
Material and surface |
Profile |
Diameter, mm |
Cross- |
Thickness |
Coating |
Coating thickness |
Embedded steel
|
Round wire |
10 |
||||
Tape or band |
75 |
3 |
||||
Hot-dip galvanized steel
|
Tape or profiled tape / plate |
90 |
3 |
500 | 63 | |
|
||||||
Round rod is mounted vertically |
16 | 350 | 45 | |||
Round wire-is mounted horizontally |
10 | 350 | 45 | |||
piped |
25 | 2 | 350 | 45 | ||
Twisted (embedded in concrete) |
70 | |||||
Two-way profile is mounted vertically |
(290) | 3 | ||||
Steel in a copper shell |
Round rod is mounted vertically |
(15) | 2000 | |||
Steel with galvanic |
Round rod |
14 | 2502 | |||
Round wire |
(8) | 70 | ||||
The band |
90 | 3 | 70 | |||
Stainless steel |
Tape or profiled tape / plate |
|||||
Round rod |
16 | |||||
Round wire |
10 | |||||
Piped |
25 | 2 | ||||
Copper |
Tape |
50 |
2 | |||
Round wire |
(25)1 50 |
|||||
Solid round rod |
(12) 15 |
When using stranded copper wire or round copper wire, mounted horizontally, the use of materials with the cross section of 16 mm is allowed. The rule is valid for the cases where the risk of corrosion and mechanical damage is negligible.
Special cases:
1 Dimensions in the brackets are only applied for protection against electric shock, while the dimensions outside the brackets are applicable for protection against lightning and electrical shock.
2 When taking necessary precautions to avoid mechanical damage of copper during the mounting process,the use of round bars with 100 mm coating is allowed.
Select and mount the grounding correctly! Take advantage of the ready-made kits by ZANDZ:
- Single-family house grounding kit ZZ-6
- Modular grounding kit ZZ-000-015
- Electrolytic grounding kit ZZ-100-102
See also:
- How to make lightning protection in a single-family house?
- Gas boiler / gas pipeline grounding
- Is it possible to install grounding in winter?
Related Articles: