Modular grounding is designed for the installation of grounding devices (the grounds) at residential buildings (houses or cottages), mobile and fixed telecom operators or energy facilities, as well as industrial enterprises.

Such ground is an assembled structure consisting of interconnected steel rods having a length of 1.5 meters covered with a layer of copper.

 

Modular grounding advantages

The advantages of modular rod design are:
the ease of elecrode installation up to a depth of 30 meterswithout the use of special machinery or tools. All operations are carried out by one person. A greater depth means a very effective grounding.
Small area occupied by the grounding devices allows to install them in the basements of houses or near the walls just as one spot. The compact size minimizes earthwork volumes.

  • All parts are connected without welding *
  • The commercial-scale production of the parts means the following:
  • excellent corrosion resistance of all parts, resulting in the service life of up to 100 years.
  • full resistance of copper-bonded rods to mechanical damage (e.g., bending and bond liftoff) during installation, which allows carrying out installation works in soils containing gravel or small particles of construction debris

(thanks to the technology of electrolytic deposition of copper  to steel).

* Connecting grounding device parts NOT made of ferrous metal  is allowed by Technical memo 11/2006 of RosElectroMontazh Association (document link)

Grounding kits

Various ready-made components of ZANDZ modular grounding kits with required specifications (e.g. to acheive a required value of grounding resistance). Such kits include all the parts necessary for the installation of a grounidng rod.

All components are easily connected to each other.

Such off-the-shelf kits are manufactured in five varieties that differ in the total length of rods, designation and contents:

ZZ-000-015 -

A universal ground for the installation as a modular electrode: one device for a depth of 15 m or three devices for a depth 5 m each
(4.5+ 4.5+6 m).

It is used as a ground with a low spreading resistance and as a lightning protection ground at a certain facility.

 


 

ZZ-000-030 -

Universal grounding device for the installation as a modular electrode: one electrode for a depth of 30 m or three electrodes for a depth of 10 meters each
(10.5+10.5+9 m).

It is used as a grounding device with a very low spreading resistance and as a lightning protection device.

 


 

ZZ-000-045 -

A multi-electrode ground consisting of 15 assembled ground electrodes for a depth of 3 m each.

This is used as a distributed ground with a low touch voltage.

 


 

ZZ-000-424 -

A ground for the installation at containerized telecom and energy supply facilities 
(4 assembled electrodes 6 m each).

 


 

ZZ-000-636 -

A ground for the installation at containerized telecom and energy supply facilities 
(4 assembled electrodes having a length of 6 m each).

 

Deep ground
(ZZ-000-015
and ZZ-000-030 kits)

Traditional ground
(ZZ-000-045 kit)

Special ground
(ZZ-000-424
and ZZ-000-636 kits)

Deep ground

Traditional ground

Special ground

A small number of vertical electrodes installed at a great depth

A large number of vertical electrodes installed at a shallow depth

Installation of grounding for containerized facilities

 

 List of components

 

 ZZ-000-015 

 ZZ-000-030 

Threaded copper-bonded grounding rod (D14; 1.5 m)

10

20

Threaded coupler, pcs

10

20

Grounding tip, pcs

3

3

Driving head for a jackhammer tup, pcs

2

3

Conductor clamp , pcs

3

3

Conductive paste, pcs

1

1

Waterproofing tape, pcs

1

1

Jackhammer tup (SDS max), pcs

1

1

 

 

 ZZ-000-045 

 ZZ-000-424 

 ZZ-000-636 

Threaded copper-bonded grounding rod (D14; 1.5 m)

30

16

24

Threaded coupler , pcs

16

16

24

Grounding tip, pcs

15

4

6

Driving head for a jackhammer tup, pcs

5

3

3

Conductor clamp , pcs

15

4

6

Conductive paste, pcs

1

1

1

Waterproofing tape, pcs

5

2

2

Jackhammer tup (SDS max), pcs

1

1

1

Customized kits

Off-the-shelf modular grounding ZANDZ kits is a universal solution for typical cases. Any desired number of components can be included  into the kit if necessary (customized kits are available upon request).

 

Buy

ZANDZ modular grounding can be purchased both as off-the-shelf kits and as separate components.

To receive information about the cost of goods, send a request to info@zandz.com .

Components

Threaded copper-bonded ground rod
Enlarge photo

Threaded copper-bonded ground rod (D14; 1.5 m)

This is a drawn steel rod with a diameter of 14 mm and a length of 1.5 meters covered with 99.9%  purity copper using electrolytic deposition method to form a coating of molecular and unbreakable bond with steel.

In addition to its role as a conductor, high-quality steel in this ground performs a mechanical role necessary to drive the electrode into the soil. The rods have a high tensile strength of 600 N / mm², and can be driven to a greater depth (up to 40 meters) into the soil using a jackhammer .

The thickness of copper bonding is at least 0.250 mm throughout the entire length of the rod (including the thread). This ensures the coating's resistance to bending, peeling and scratching during installation. This is especially important for the thread where a thinner layer of copper would be completely destroyed by loads and friction with the coupler when the rod is driven into the soil.

These features guarantee a high corrosion resistance and ensure the ground rods long service life (up to 100 years).

Threads at the sides of each rod were formed by a roll threading process for the interconnection of rods through a coupler.

 

 

ZZ-001-065

Weight:

1.9 kg

Length:

1.51 m

Rod diameter:

14 mm

Thread diameter:

16 mm

 

Details about manufacturing and testing technology of the coating are available on a separate page.

 

Threaded coupler
Enlarge photo

 

Threaded coupler

This brass coupler is used for the interconnection of rods. It is made in such a way that the rods come into contact with each other in the very center of the coupler and the energy necessary to drive the rods into the soil is not not transferred to the coupler. Thus, there is no shock pulse "scattering" and mechanical stress is taken away from the coupler.

 

 

ZZ-002-061

Weight:

0.082 kg

Length:

60 mm

Diameter:

21 mm

 

Grounding tip
Enlarge photo

 

Grounding tip

The pointed steel tip facilitates driving the rods into a strong soil.

 

 

ZZ-003-061

Weight:

0.074 kg

Length:

50 mm

Diameter:

22 mm

 

Driving head
Enlarge photo

 

Driving head for a jackhammer tup

The head facilitates driving the ground rods and increases the operational safety of both people and tools.

The head is attached to the ground rod through a coupler during installation. The head sizes are selected in such a way that the driving force does not damage the coupler, i.e. the impact impulse is transmitted directly to the rod, not to the coupler.

 

 

ZZ-004-060

Weight:

0.088 kg

Length:

55 mm

Diameter:

25 mm

 

Conductor connection clamp
Enlarge photo

 

Conductor connection clamp

This is a stainless steel profiled clamp with M10 bolts. It allows connecting a copper-bonded rod to a grounding conductor, i.e. to a round cross-section wire or strip (40 mm wide).

The safe use of steel and galvanized wire is possible. For that purpose, a gasket is put inside the clamp, which prevents the formation of electrochemical binding between steel / zinc and copper.

To prevent loosening of "bolt-nut" threaded joints spring washers are used ( Grover washers) installed between the clamping surface and the nut.

 

 

ZZ-005-064

Weight:

0.158 kg

Length:

70 mm

Width:

70 mm

Height:

30 mm

 

Conductive paste
Enlarge photo

 

Conductive paste

The paste is used to reduce the electrical resistance between the rods and couplers, as well as for added corrosion protection of the rod ends (in the coupler). The paste is also used for the guiding head to facilitate its removal after a rod was driven. During installation, the paste is applied to the threaded parts.

 

 

ZZ-006-000

Total weight:

0.152 kg

Paste weight:

0.100 kg

Height:

200 mm

Width:

60 mm

Thickness:

50 mm

 

Waterproofing tape
Enlarge photo

 

Waterproofing tape

The tape is used to protect the connection of rod and grounding conductor from electrochemical and soil corrosion by complete displacement of water (moisture) from the connection point to make corrosion impossible. The tape retains its physical and mechanical qualities for many years.

It is made of non-woven synthetic fiber material, impregnated and coated with a neutral compound based on a saturated oil hydrocarbon (petrolatum) and an inert silicon-containing filler. The tape remains soft under the influence of a wide range of temperatures. It does not harden or crack. The tape is highly resistant to mineral acids, alkali, salts and microorganisms, highly hermetical against water, steam and gas.

Only conductor connection clams are protected using the tape.

 

 

ZZ-007-030

Weight:

0.422 kg

Tape height:

30 mm

Coil diameter:

150 mm

Length in the coil:

10 m

 

Jackhammer tup (SDS-max)
Enlarge photo

 

Jackhammer tup (SDS-max)

This steel tup with tempered head transmits the force from the jackhammer to the driving head (i.e. to the rods being driven). It is used with hammers equipped with SDS-Max fastening.

 

 

ZZ-008-000

Weight:

0.478 kg

Length:

250 mm

Diameter:

18 mm

 

 

Additional components

Grounding conductor
Enlarge photo

Grounding conductor (PV-1 25 mm²)

This copper single-core, bunched and multicore conductor with a cross section 4 to 185 mm² in PVC insulation is used to connect the ground electrode to the facility (main grounding bus in the board).

The conductor comes in measured lenghts and in off-the-shelf coils  with 3/5/10 meters  of cable
(ZZ-500-103 / ZZ-500-105 / ZZ-500-110), with a cable terminal for D8 bolt  on one end to connect to the main ground bus in the electic board.

Coils

ZZ-500-103

ZZ-500-105

ZZ-500-110

Length:

3 m

5 m

10 m

Weight:

1.4 kg

2.3 kg

4.55 kg

External diameter:
(with insulation)

7.5 mm

7.5 mm

7.5 mm

Bolt hole diameter:

8 mm

8 mm

8 mm

Please visit a a separate page for the dimensions and prices of all the cables supplied.

 

Copper-bonded steel wire
Enlarge photo

Copper-bonded steel wire
(D 8mm/S 50mm²)

The wire is used as lightning protection rods and down conductors.

The quality and the look of pure copper at a lower price!

 

 

ZZ-11149

Weight of 1 meter:

0.41 kg

Diameter:

8 mm

 

 

Copper-bonded steel wire
Enlarge photo

Copper-bonded steel wire
(D 10mm / S 80 mm²)

The wire used as a grounding conductor.

The quality and the look of pure copper at a lower price!

 

 

ZZ-11150

Weight of 1 meter:

0.63 kg

Diameter:

10 mm

 

 

Inspection pit
Enlarge photo

Inspection pit (plastic)

The plastic pit is used to facilitate access to the connection between the electrode (rod) and the grounding conductor. It is installed above the place of connection flush with the soil.

 

 

GL-11402

Weight:

2 kg

Length:

258 mm

Width:

258 mm

Height:

215 mm

 

 

Inspection pit
Enlarge photo

Inspection pit for all soil types (plastic)

The polypropylene pit is used to facilitate access to the connection between the electrode (ground rod) and the grounding conductor. It is installed above the place of connection flush with the soil.

 

 

GL-11404

Weight:

2.6 kg

Length:

290 mm

Width:

240 mm

Height:

205 mm

 

 

Straightening device
Enlarge photo

Straightening device

The device is used for straightening of wire having a diameter of 6 to 10 mm and the grounding tape with a width of 20 to 45 mm and a thickness of 3 to 4 mm.

 

 

ZZ-510-700

ZZ-510-900

Weight:

14.5 kg

12 kg

Length:

0.3 m

0.6 m

Width:

0.3 mm

0.2 mm

Height:

0.15 mm

0.2 mm

Number of rollers

7 pcs

9 pcs

 

 

Manual tape bender
Enlarge photo

Manual tape bender

The manual bender is used for the bending  of grounding tapes up to 40 mm wide and up to 8 mm thick and wire having a diameter of up to 10 mm.

 

 

ZZ-511-600

Weight:

3.2 kg

Length:

0.6 m

Width:

0.1 mm

Height:

0.1 mm