Appendix № 1 to "Economic justification of using ZANDZ modular grounding"
The activities were carried out in accordance with the EIC 7 th ed. Chapter 1.7.
The object of the protective grounding installation a unit transformer substation (UTS) with the voltage of 10/0,4 kW. According to the customer's data, the ground in the intended place of grounding devices installation is clay loam. Specific soil resistance is taken equal to 100 Ohm ∙ m.
In accordance with the
In accordance with EIC 1.7.101
The set of measures to ensure the necessary requirements to the grounding device is represented by the following solutions:
- installation of 30 vertical electrodes 3 m long of angle steel of 50x50x5 mm (GOST 8509-93), united by a horizontal contour of steel tape with the cross-section of 5x32 mm (GOST 103-2006), laid around the UTS. Depth of the tape burial 0.7 m;
- a horizontal ground electrode 1 meter long is laid to the wall of the UTS (copper-bonded tape with cross-section of 5x32 mm).
Arrangement of elements of the grounding device is shown on Figure 1.

Figure 1 - grounding device elements layout
Условные обозначения – code designations
Вертикальный электрод длиной 3 м – vertical electrode 3 m long
Горизонтальный электрод – horizontal electrode
Calculation of a grounding device resistance:
Horizontal electrode resistance:

ρ - soil resistivity, Ohm* m;
b - horizontal electrode tape width,m;
Lгор - horizontal electrode length, m.
Vertical electrode resistance:

ρ - soil resistivity, Ohm* m;
b - horizontal electrode tape width,m;
h- depth of horizontal mesh laying,
Lгор

t – deepening of the electrode top, m
Impedance of the grounding device:

Where n - number of kits;
kисп - utilization ratio;

The design resistance of the grounding device is 3.55 ohms.
The list of required materials:
| № | Product | Dimensions | Quantity |
| 1. | Hot-rolled steel equal-flange grounding angle GOST 8509-93 | 50x50x5 length of 3 m | 30 pieces. |
| 2. | Hot-rolled steel tape for grounding GOST 103-2006 | 5x32 | 93 m |
See further - Appendix № 2. Local costing № 030 (application of ZANDZ modular grounding of vertical stainless steel rods with the diameter of 16 mm and 1,5 long).
Do you need to make the project on grounding and lightning protection? Order it by contacting the ZANDZ Technical Center!
You may be interested in:
- Useful materials for designers: articles, recommendations, examples
- Free webinars with the leading industry experts
- Design of grounding and lightning protection (projects in DWG and PDF formats)
- Calculation formulas for a grounding device
- Examples of grounding and lightning protection solutions for large objects
Related Articles: