We calculate grounding and lightning protection for a church!

A client turned for help to our company to calculate grounding and lightning protection for a church in Moscow.

church                      
The task was as follows: 

Make a lightning protection system of a church, as well as a ground loop for the church and a household building. A grounding device for the grounding and lightning protection was made separately. Two offering options were needed: one on the basis of electrolytic ZZ-100-102MB grounding kits and the other on the basis of a ZZ-000-030 modular grounding kit. 
Building dimensions:

  • Length: 36.9 m;
  • Width: 24.4 m;
  • Wall height from the ground level: 15.5 m;
  • Ridge height from the ground level: 42.5 m.

The church has a complex shape of the roof with a cross and a dome on it. The roof is made of copper. The building also has 20 rain pipes arranged on the facade.
Soil type: sand.

 

Calculations were performed in accordance with PUE 7th ed., SO 153-34.21.122-2003 "Instructions for lightning protection of buildings, structures, and industrial communications" (hereinafter SO) and RD 34.21.122-87 "Instruction for the lightning protection of buildings and structures" (hereinafter RD).
The church is a normal building in terms of lightning protection according to SO and has Category 3 according to RD.
The protection of buildings against lightning strikes is carried out by lightning rods. A lightning rod is a device that rises above the protected facility to divert the lightning current into the soil without entering the protected facility. In this case, a cross on top of the church will act as a lightning rod.

The two grounding and lightning protection options for the church are described below.

Option 1. Based on ZZ-100-102MB electrolytic grounding.

As the type of soil at the facility is sand with the resistivity equal to 1500 ohm/m, ZANDZ ZZ-100-102MB electrolytic grounding specifically designed for use in high-ohm soils is proposed as a grounding device.

After calculations based on standard documents, technical specifications, and the required values, ZANDZ experts proposed a set of measures to ensure the necessary requirements for the grounding device:

  1. installing two down conductors using copper-bonded wire D = 8 mm.
  2. installing ZANDZ ZZ-100-102MB kits electrolytic grounding. The kits are connected using a copper-bonded tape 30x4 mm in cross-section. The tape laying depth is 0.5-0.8 m;
  3.  
  4. the electrodes must be placed at a distance at least 6 meters from each other, from the foundations of buildings and other engineering structures.

churt-1

RU

EN

- Полоса омедненная (GL-11075-50)

- Copper-bonded tape (GL-11075-50)

 

church=2

RU

EN

Проволока омедненная (GL-11149-50)

Copper-bonded wire (GL-11075-50)

Полоса омедненная (GL-11075-50)

Copper-bonded tape (GL-11075-50)

Зажим для соединения токоотводов (GL-11551A)

Down conductor connection clamp (GL-11551A)

Зажим контрольный для соединения токоотводов (GL-11562A)

Down conductor control connection clamp (GL-11562A)

Зажим на водосточный жолоб для токоотвода (GL-11545A)

Down conductor-to-gutter clamp (GL-11545A)

Зажим для токоотводов (GL-20022)

Down conductor clamp (GL-20022)

Зажим к фасаду для токоотвода (GL-1173A)

Down conductor-to-façade clamp (GL-1173A)

ЗОНА ЗАЩИТЫ

PROTECTION ZONE

 

Equipment list:​

 

Option 2. On the basis of ZZ-000-030 modular grounding kit.

The second option is similar to the first one, but more ZANDZ ZZ-000-030 modular grounding kits are needed. The set of measures to ensure the necessary requirements for the grounding device is represented by the following solutions:

  1. installing two down conductors using copper-bonded wire D = 8 mm.
  2. installing ZANDZ ZZ-000-030 modular grounding kits. The kits are connected using a copper-bonded tape 30x4 mm in cross-section. The tape laying depth is 0.5-0.8 m;
  3. the electrodes must be placed at least 6 meters from each other, from the foundations of buildings and other engineering structures.

 

RU

EN

- Полоса омедненная (GL-11075-50)

- Copper-bonded tape (GL-11075-50)

 



church

RU

EN

Проволока омедненная (GL-11149-50)

Copper-bonded wire (GL-11075-50)

Полоса омедненная (GL-11075-50)

Copper-bonded tape (GL-11075-50)

Зажим для соединения токоотводов (GL-11551A)

Down conductor connection clamp (GL-11551A)

Зажим контрольный для соединения токоотводов (GL-11562A)

Down conductor control connection clamp (GL-11562A)

Зажим на водосточный жолоб для токоотвода (GL-11545A)

Down conductor-to-gutter clamp (GL-11545A)

Зажим для токоотводов (GL-20022)

Down conductor clamp (GL-20022)

Зажим к фасаду для токоотвода (GL-1173A)

Down conductor-to-façade clamp (GL-1173A)

ЗОНА ЗАЩИТЫ

PROTECTION ZONE

 

Equipment list:​

 

Do you want to obtain similar calculations for your facility? Contact us and we will surely help!