25.06.15 , , ,
The requests for calculation of grounding and lightning protection that our technicians receive, there are cases and organization of grounding and lightning protection systems for medical institutions: hospitals and medical centers. In addition to the "standard" grounding contour for the entire electricity mains of the building, customers almost always ask to calculate a separate grounding device for the specific equipment (body scanner, X-ray, cardiograph etc).
So we decided to tell you about calculation of grounding and lightning protection for medical institutions on a real example.
It could not have come at a better time, but, recently, our technicians received such a request to identify a set of measures for the protection and operation of equipment at a medical center in Moscow.
Task:
- perform lightning protection system (step 6x6 m) and a grounding device (GD) that provides resistance of 4 ohms;
- perform separate grounding device with the resistance of 2 Ohm for an X-ray machine.
Type of soil - clay loam (100 Ohm * m), available area for the installation of an independent grounding device - 15x15 m.
The solution is based on the following measures:
- Organization of lightning protection mesh with the help of copper-bonded steel wire D = 8 mm.
- Arrangement of down conductors with the use of copper-bonded wire D = 8 mm. See figure below.
- Installation of the first (4 Ohm) grounding device, which consists of eight vertical electrodes 3 m in length, combined by a horizontal electrode (copper-bonded wire D = 10 mm). The distance from the electrode to the walls of the building is not less than 1 m, embedding 0.5 - 0.7 meters.
-
-
Проволока омедненная - copper bonded wire
-
The second grounding device (2 Ohm) is designed as a grounding mesh (copper-bonded wire D = 10 mm) consisting of four cells with the step of 7x7 m each. Vertical electrodes 6m long are mounted at the intersection points of the horizontal conductor. Embedment to 0.5 - 0.7 m. Distance from the building not less than 10 m. It is necessary to isolate the horizontal conductor (grounding device not more than 2 Ohm) at the to eliminate possible interference. See figure below.
Объект - object
Электрод - electrode
Проволока омедненная - copper bonded wire
-
Full list of equipment:
1 |
GL-11149-50 |
GALMAR Copper-bonded wire (D 8mm / S 50 mm²; coil 50 meters) |
13 |
|
2 |
GL-11150-50 |
GALMAR Copper-bonded wire |
2 |
|
3 |
GL-11150-20 |
GALMAR Copper-bonded wire |
1 |
|
4 |
GL-11551A |
GALMAR Clamp for the connection of down conductors (painted galvanized steel) |
100 |
|
5 |
GL-11706 |
GALMAR Holder on a flat roof for down conductor (D8 mm; for bonding, plastic) |
500 |
|
6 |
GL-11703A |
GALMAR Clamp to the facade of down conductor (painted galvanized steel) |
150 |
|
7 |
GL-11562A |
GALMAR Contorl clamp for the connection of down conductors wire + tape (painted galvanized steel) |
8 |
|
8 |
ZZ-001-065 |
52 |
||
9 |
ZZ-002-061 |
36 |
||
10 |
ZZ-003-061 |
17 |
||
11 |
ZZ-004-060 |
11 |
||
12 |
ZZ-006-000 |
4 |
||
13 | ZZ-008-000 | ZANDZ Breaker hammer header (SDS max) | 1 | |
14 | ZZ-005-064 | ZANDZ Сlamp for conductor connection (up to 40 mm) |
20 | |
15 | ZZ-007-030 | ZANDZ Waterproof tape | 5 |
The activities are carried out in accordance with the EIC 7th ed., industry standard 153-34.21.122-2003 "Instructions for lightning protection of buildings, structures and industrial communications" (hereinafter industry standard), and AD 34.21.122-87 "Instructions for lightning protection of buildings and structures".
Will you also need calculation of grounding or lightning protection? Contact us and we will surely help!
See also:
Related Articles: