Grounding and lightning protection for a medical center

All news

25.06.15                        , , , 

Grounding and lightning protection for a medical center

The requests for calculation of grounding and lightning protection that our technicians receive, there are cases and organization of grounding and lightning protection systems for medical institutions: hospitals and medical centers. In addition to the "standard" grounding contour for the entire electricity mains of the building, customers almost always ask to calculate a separate grounding device for the specific equipment (body scanner, X-ray, cardiograph etc).

So we decided to tell you about calculation of grounding and lightning protection for medical institutions on a real example.

It could not have come at a better time, but, recently, our technicians received such a request to identify a set of measures for the protection and operation of equipment at a medical center in Moscow.

Task:

  • perform lightning protection system (step 6x6 m) and a grounding device (GD) that provides resistance of 4 ohms;
  • perform separate grounding device with the resistance of 2 Ohm for an X-ray machine.

Type of soil - clay loam (100 Ohm * m), available area for the installation of an independent grounding device - 15x15 m.

 

The solution is based on the following measures:

  1. Organization of lightning protection mesh with the help of copper-bonded steel wire D = 8 mm.
  2. Arrangement of down conductors with the use of copper-bonded wire D = 8 mm. See figure below.
  3. Installation of the first (4 Ohm) grounding device, which consists of eight vertical electrodes 3 m in length, combined by a horizontal electrode (copper-bonded wire D = 10 mm). The distance from the electrode to the walls of the building is not less than 1 m, embedding 0.5 - 0.7 meters.
  4.  

  5. The solution is based on the following measures

  6. Проволока омедненная - copper bonded wire

  7. The second grounding device (2 Ohm) is designed as a grounding mesh (copper-bonded wire D = 10 mm) consisting of four cells with the step of 7x7 m each. Vertical electrodes 6m long are mounted at the intersection points of the horizontal conductor. Embedment to 0.5 - 0.7 m. Distance from the building not less than 10 m. It is necessary to isolate the horizontal conductor (grounding device not more than 2 Ohm) at the to eliminate possible interference. See figure below.

The second grounding device (2 Ohm)

Объект - object

Электрод - electrode

Проволока омедненная  - copper bonded wire

  1. Full list of equipment:

 

The activities are carried out in accordance with the EIC 7th ed., industry standard 153-34.21.122-2003 "Instructions for lightning protection of buildings, structures and industrial communications" (hereinafter industry standard), and AD 34.21.122-87 "Instructions for lightning protection of buildings and structures".

Will you also need calculation of grounding or lightning protection? Contact us and we will surely help!



Related Articles: