Lightning protection of a diesel fuel storage warehouse in Samara

Lightning protection of a diesel fuel storage warehouse in Samara

An integral component in the construction of an explosive facility or structure is lightning protection. But what if a taller building is located nearby such an object?

 

In this case, this building is used as a natural lightning rod. A request was received by  ZANDZ Technical Center for the calculation of lightning protection systems for a warehouse for diesel fuel storage in the city of Samara.

The measures were performed in accordance with:

Warehouse refers to the “special, representing a danger to the immediate environment”, in accordance with the IS and to the 2nd category, according to AD.

Source data:

- object: diesel fuel storage warehouse;
- location region: city of Samara;
- measures of the protected object: 1,05х2,05х2,5 m;
- tank material – profiled sheet not less than 1 mm thick;
- there is a garage 5,3 m from the object, it is 7,87 m high;
- soil resistivity – 150 Ohm*m.

The set of measures to ensure the necessary requirements for a lightning protection system for a warehouse for diesel fuel storage is presented by the following solutions:

  • installation of a vertical air terminal mast with a height of 1.5 m (GL-21134) to the facade of the container on one side, on the opposite side a garage building is used as an air terminal (natural) (see Fig. 1);
  • installation of a grounding device, according to AD, p.2.2g., consisting of 3 vertical electrodes 3 m long, united by a horizontal electrode (copper-bonded tape 30x4 mm) along the contour of the warehouse. The distance from the horizontal electrode to the object is at least 1 m, burial depth is 0.5 - 0.7 meters.
 

Calculation of the resistance of the grounding device:

Vertical electrode resistance:

Vertical electrode resistance

where ρэкв – equivalent soil resistivity - 150 Ohm·m;
L – vertical electrode length - 3 m;
d – vertical electrode diameter - 0,014 m;
T – deepening – distance from the ground surface to the ground electrode – 2 m;

Deepening of the electrode

where t  – deepening of the electrode top - 0,5 m

 

Horizontal electrode resistance:

Horizontal electrode resistance

where ρ – soil resistivity - 150 Ohm·m;
b – horizontal electrode width - 0,03 m;
h – horizontal electrode laying depth - 0,5 m;
Lгор – horizontal electrode length - 14 m.

 

Grounding device impedance:

Grounding device impedance

where n – number of kits, vertical ground electrodes - 3 pc, horizontal electrode – 1 pc. ;
Kисп – utilization ratio, 0,65;

The rated resistance of the grounding device is 13.26 ohms.

 

The results of the calculation of the protection zone in accordance with IS:

Air-terminal mast №1  (GL-21134):

h = 3,7 m;

Height of the cone according to IS table 3.4:

Height of the cone according to IS table 3.4

Radius of the cone according to IS table 3.4:

Radius of the cone according to IS table 3.4

 

Air-terminal mast №2  (Garage):

h = 7,87 м;

The height of the cone according to IS table 3.4:

https://zandz.com/catalog_files/news/News/images/molniezashchita-sklada-dlja-hranenija-diztopliva-v-samare-formula7.png

The radius of the cone according to IS table 3.4:

https://zandz.com/catalog_files/news/News/images/molniezashchita-sklada-dlja-hranenija-diztopliva-v-samare-formula8.png

The distance between the lightning rods:

L = 7,35 м;

Ultimate distance between the lightning rods, according to IS, table.3.6 (we take the height of the lowest lightning rod):

Ultimate distance between the lightning rods

There is no dip height.

The equipment location and protection zone are shown in Figure 1.

The list of equipment and necessary materials is given in table 1.

 

Equipment location

 
  • Молниеприемник-мачта высотой 1, 5 м – Air-terminal mast 1,5 m high
  • Проволока омедненная стальная диаметров 8 мм – Copper-bonded steel tape 8 mm in diameter
  • Полоса омедненная стальная сечением 30*4 мм – Copper-bonded steel tape with the cross-section of 30*4 mm
  • Электрод  - Electrode

Figure 1 – Equipment location.

Table 1 – List of material needs.

 

Picture

Product item

Name

Quantity, pieces

1.

GL-21134

GL-21134

GALMAR Air-terminal mast (1,5 meters: for vertical surfaces: galvanized steel)

1

2.

GL-11149-10

GL-11149-10

GALMAR Copper-bonded tape (D 8 мм / S 50 мм²; coil of 10 meters)

1

3.

GL-11704A

GL-11704A

GALMAR Clamp to the façade for down conductor (painted galvanized steel)

3

4.

ZZ-001-065

ZZ-001-065

ZANDZ Copper-bonded threaded grounding rod (D14; 1,5 м)

6

5.

ZZ-002-061

ZZ-002-061

ZANDZ Threaded connecting coupler

4

6.

ZZ-003-061

ZZ-003-061

ZANDZ Starting tip

3

7.

ZZ-004-060

ZZ-004-060

ZANDZ Driving head for a breaker hammer

2

8.

ZZ-006-000

ZZ-006-000

ZANDZ Conductive grease

1

9.

ZZ-008-000

ZZ-008-000

ZANDZ Head for a breaker hammer (SDS max)

1

10.

ZZ-005-064

ZZ-005-064

ZANDZ Clamp for connecting conductor (up to 40 mm)

5

11.

ZZ-007-030

ZZ-007-030

ZANDZ Hydro-insulation tape

2

12.

GL-11075-20

GL-11075-20

GALMAR Copper-bonded tape (30*4 mm / S 120 mm²; coil of 20 meters)

1

Do you have questions on grounding and lightning protection of a warehouse for storing diesel fuel? Contact ZANDZ Technical Center!