Overvoltage protection in single and three-phase voltage circuits [230 / 400V] 50 Hz.

The most important characteristic of Class 1 arresters is their ability to drain Iimp lightning current (pulse form 10/350 ms).

The devices in this series are intended for installation in zones 0A-1 in accordance with the concept of protection zones (IEC 61312).

  • voltage protection level Up≤4,0 and 2.5 kV;
  • patented sealed gas discharger and arc control pot;
  • no blow hole - it is not required to keep the permissible distance to other devices;
  • lightning current limit up to 100 kA (10/350 ms);
  • V-shaped connection is possible;
  • no leakage currents - possible installation before the counter;
  • optional remote signaling contact (FM version);

Single-pole SPD of class 1

CT-T1+2/1+0-350-FM

CT-T1/1+0-350-FM

One-pole SPD designed to protect low-voltage electrical equipment

  • maximum lightning impulse current (10/350 ms) Iimp: 25 k╤В╨е╨╕тХи╨░;
  • limit voltage Up: not more than 2.5 kV;

SPD of class 1 for use in single-phase networks with TN neutral mode

CT-T1/2+0-350-FM

SPD for use in single-phase networks with TN neutral mode and rated voltage of 230V, 50 Hz

  • maximum lightning impulse current (10/350 ms) Iimp 50 k╤В╨е╨╕тХи╨░;
  • limit voltage Up not more than 2.5 kV;

PowerPro B TN

SPD for use in single-phase networks with TN neutral mode and rated voltage of 230V (50 Hz)

  • maximum lightning impulse current (10/350 ms) Iimp 50 k╤В╨е╨╕тХи╨░;
  • limit voltage Up not more than 4.0 kV;

SPD of class 1 for use in three-phase networks with TN-C neutral mode

CT-T1/3+0-350-FM

Combined SPD for use in three-phase networks with TN-C neutral mode and rated voltage of 230 V, 50 Hz

  • maximum lightning impulse current (10/350 ms) Iimp 75 k╤В╨е╨╕тХи╨░;
  • limit voltage Up not more than 2.5 kV;

PowerPro B TNC

Combined SPD for use in three-phase networks with TN-C neutral mode and rated voltage of 230/400 V (50 Hz)

  • maximum lightning impulse current (10/350 ms) Iimp 50 k╤В╨е╨╕тХи╨░;
  • limit voltage Up not more than 4.0 kV;

SPD of class 1 for use in three-phase networks with TN-S neutral mode

CT-T1/3+1-350-FM

SPD for use in three-phase networks with TN-S neutral mode and rated voltage of 230 V, 50 Hz

  • maximum lightning impulse current (10/350 ms) Iimp 100 k╤В╨е╨╕тХи╨░;
  • limit voltage Up: not more than 2.5 kV;

PowerPro B TNS

SPD for use in three-phase networks with TN-S neutral mode and rated voltage of 230/400 (400/690) V (50 Hz)

  • maximum lightning impulse current (10/350 ms) Iimp 100 k╤В╨е╨╕тХи╨░;
  • limit voltage Up not more than 4.0 kV;

SPD of class 1 for use in three-phase networks with TT neutral mode

PowerPro B TT

SPD for use in three-phase networks with TT neutral mode and rated voltage of 230/400 V (50 Hz)

  • maximum lightning impulse current (10/350 ms) Iimp 100 k╤В╨е╨╕тХи╨░;
  • limit voltage Up not more than 4.0 kV;