How to perform grounding and lightning protection of a diesel generator unit?

Diesel Generator Units (DGU), placed in a shipping container, are widely used for power supply of temporary facilities, as well as a backup power source. The generators in this design require the same grounding device, as well as other sources with the voltage of 380 V. Let's find out how to perform grounding and lightning protection for them?

An example of a diesel generator unit
An example of a diesel generator unit

In accordance with the EIC 7 th ed. Chapter 1.7, grounding resistance should be not more than 4 ohms. The contour can be laid around the container, and when installing lightning protection it can also be used for spreading lightning currents. The decision, which reflects the objectives of these systems doesn't require a large area - the ground electrode is located on the container perimeter at the distance of one meter and is complemented by vertical electrodes. Below you will see the detailed calculation and arrangement of grounding and lightning protection for a container with a diesel generator unit, located in Skolkovo.
 
Set of measures for lightning protection:

  1. You install two air-terminal masts for mounting to vertical surfaces 1.5m high, fixation of which is carried to the container wall. It is considered that the 0.3m of the bar length goes to the fixation.
  2. From each air terminal two down conductors are placed with the use of copper-bonded wire D = 8 mm, which are connected with an artificial ground electrode. Fixation of down conductors to the well is carried out by means of clamps GL-11704A (0.6-1 m setting increment). The down conductors are fixed on the roof with GL-11747A clamps.

A set of activities for grounding:

  1. A horizontal ground electrode is laid around the container. The ground electrode is made of corrosion-resistant stainless copper-bonded steel tape with the cross- section of 4x30 mm (GL-11075), laying depth 0.5 m, and distance to the wall of the building 1 m.
  2. In places of the down conductor descent, four vertical electrodes 3 m in length are installed.
  3. Connection of horizontal electrodes is carried out by using clamp ZZ-005-064.
  4. Connection of the down conductor with the output of the copper-bonded tape from the ground is carried out with the help of a control clamp GL-11562A.

Arrangement of elements of lightning protection systems and the grounding device is shown in Figures 1 and 2.
Protection zone corresponding to zone B of the AD, is shown in Figure 3.
Figure 1 - Layout of lightning protection elements and the grounding device
Figure 1 - Layout of lightning protection elements and the grounding device
Figure 2 - Sketch with the location of lightning protection elements and the grounding device
Figure 2 - Sketch with the location of lightning protection elements and the grounding device
How to perform grounding and lightning protection of a diesel generator unit
Условные обозначения- notations
Стержневой молниеприемник 1,5 м – rod lightning rod 1.5m high
Вертикальный заземлитель длиной 3 м – vertical ground electrode 3 m long
Горизонтальный заземлитель – horizontal ground electrode
Токоотвод  - down conductor
Зажим для подключения проводника – clamp for connecting conductor
Зажим контрольный – control clamp
Зажим на крышу, покрытую металлическим профилем для токоотвода – Clamp for the roof covered with metal profile for down conductor
Figure 3 - Protection zone corresponding to zone B of the AD
Figure 3 - Protection zone corresponding to zone B of the AD

Calculation of lightning protection:
The following source data are taken for the calculation:

  1. Lightning density in the ground - 4 strikes / square kilometre per year for the city of Moscow region;
  2. The number of strikes into an unprotected object - 0.0014 1/year, period - once in 714 years.

The results of lightning protection calculation performed by the software, developed by JSC "Energy Institute to the name of Krzhizhanovsky "(JSC" ENIN ") are shown in Table 1.


Table 1 - Results of lightning protection calculation

Object Height of the lightning rod, m Protection reliability The number of strikes into an object
year-1

 
The number of breakthroughs into the object,
year-1

 
Period of srikes, year Period of breakthroughs, year
1 Container 1,5 0,949 0,0024 0,00012
once in 416 years once in 8333 years

Calculation of grounding device resistance:
Estimated value of the resistivity of frozen clay ground is taken to be 60 Ohm ∙ m. As previously mentioned, in accordance with the EIC 7 th ed. Chapter 1.7.101 grounding device resistance, to which neutrals of the generator or transformer or single-phase current supply terminals are connected. At any time of the year it should not exceed 4 ohms at the line voltage of 380 V of a three-phase power source.
Calculation of grounding device resistance
The design resistance of the grounding device is 3.88 ohms, which is less than the required value of 4 ohms.
 
The list of the required materials is given in Table 2:
Table 2 - List of materials needs

Fig. Product item Product Quantity
1. GL-21134 GL-21134 GALMAR Air terminal mast (1.5 meters; for vertical surfaces, galvanized steel) 2
2. GL-11149-20 GL-11149-20 GALMAR Copper-bonded steel wire (D8 mm; coil of 20 meters) 1
3. GL-11704A GL-11704A GALMAR Clamp to the facade for down conductor (painted galvanized steel)
 
6
4. GL-11747A GL-11747A GALMAR Clamp for the roof covered with metal profile / corrugated board for down conductors (painted galvanized steel) 7
5. GL-11562A GL-11562A GALMAR Control clamp for connection of down conductors, wire + tape (painted galvanized steel) 2
6. ZZ-005-064 ZZ-005-064 ZANDZ Clamp for connecting conductor    (up to 40 mm) 4
7. GL-11075-20 GL-11075-20 GALMAR Copper-bonded tape (30 * 4 mm / S 120 mm²; coil of 20 meters)  1
8. GL-11075-10 GL-11075-10 GALMAR Copper-bonded tape (30 * 4 mm / S 120 mm²; coil of 10 meters)  1
9. ZZ-001-065 ZZ-001-065 ZANDZ Copper-bonded threaded ground rod (D14; 1,5 m) 8
10. ZZ-002-061 ZZ-002-061 ZANDZ Threaded coupler 5
11. ZZ-003-061 ZZ-003-061 ZANDZ Starting tip 4
12. ZZ-004-060 ZZ-004-060 ZANDZ Driving stud for a breaker hammer 2
13. ZZ-006-000 ZZ-006-000 ZANDZ Conductive grease 1
14. ZZ-007-030 ZZ-007-030 ZANDZ Waterproof tape 2
15. ZZ-008-000 ZZ-008-000 ZANDZ Header for a breaker hammer (SDS max) 1