Example of Lightning Protection for a Modular Building with a Turbo-Expanding Assembly Located in the Murmansk Region

In the summer of 2023, the ZANDZ.com Technical Center (ZANDZ TC) made a calculation of lightning protection for a facility related to an oil and gas condensate field complex.

According to the explosive zone classification in the IEC, a room located beyond the explosive zone should be considered non-explosive if there are no other factors exist that may result in explosion in the room. Examples of such factors are Class B-Ia rooms, which are only accessible in the event of an accident and do not normally generate explosive mixes of combustible gas. Lightning protection of such facilities is made according to Category II of RD 34.21.122-87 (RD).

Example of Lightning Protection for a Modular Building with a Turbo-Expanding Assembly Located in the Murmansk Region

The object, which lightning protection calculation was performed by TC ZANDZ, is a block-modular building of turbo-expanding assembly made of sandwich panels.  The expected lightning strike value per year is less than 1. The calculation shall be made for Zone B.

Protection zone of a double lightning arrester, RD, Appendix 3
Protection zone of a double lightning arrester, RD, Appendix 3

Lightning protection solution for the facility

Protection of buildings against lightning strikes is provided by using lightning arresters. Lightning arrester is a device that is elevated over the protected facility through which the lightning current goes into the ground bypassing the protected facility. It consists of a lightning rod that accepts the lightning discharge directly, a current collector, and a ground terminal.
A set of arrangements ensuring compliance with the lightning protection requirements is based on the following solutions:

  • two of 5 m lightning rods are installed on the wall. It is taken into account that 1 m of the height of lightning rod is necessary for mounting;
  • the lightning arresters are interconnected to create two current collectors using galvanized wire D = 8 mm from each lightning arrester;
  • current collectors are attached (with mounting step 0.6 to 1 m):
    • on the roof and the wall using clamps ZZ-11747;
  • current collectors are connected and branched using clamps ZZ-11551.

Solution for protective grounding

A set of measures to ensure the necessary requirements for the earthing device is represented by the following solutions:

  • installation of a 3 m grounding arrangement consisting of a horizontal electrode (steel galvanized bar 4 x 30 mm), depth 0.5 m and 3 vertical electrodes (14 mm diameter copper-plated steel rods);
  • interconnection of vertical and horizontal electrodes is carried out using clamps ZZ-005-064;
  • connection of current collectors with the output of a galvanized bar from the ground is made using clamps ZZ-202-013;
  • design of the grounding arrangement corresponds to item 1.7.55 of the EIC. Grounding arrangements for protective grounding and grounding for lightning discharges are common.

The location of the elements of the lightning protection system and the grounding arrangement is shown in a drawing in a separate file. The indicated protection zone corresponds to zone B according to RD.

Alt- Layout of the lightning protection and grounding arrangement elements
View full-size image

The list of materials used is provided in Table 1.

Table 1. The list of required materials

Item No. Fig. Part number Product Amount
Lightning protection system
         
1 ZANDZ Vertical lightning mast, 5 m (stainless steel) ZZ-201-005 ZANDZ Vertical lightning mast, 5 m (stainless steel) 2
2 ZANDZ Wall fastening for lightning rod (stainless steel) ZZ-203-001 ZANDZ Wall fastening for lightning rod (stainless steel) 2
3 ZANDZ lightning rod clamp for current collectors (stainless steel) ZZ-202-001 ZANDZ lightning rod clamp for current collectors (stainless steel) 2
4 ZANDZ galvanized steel wire (D 8 mm / S 50 mm²; wire bundle 125 m) ZZ-502-008-125 ZANDZ galvanized steel wire (D 8 mm / S 50 mm²; wire bundle 125 m) 1
5 ZANDZ Facade/wall clamp for 8 mm current collector with elevation (stainless steel) ZZ-11747 ZANDZ Facade/wall clamp for 8 mm current collector with elevation (stainless steel) 60
6 ZANDZ Clamp for connecting current collectors (D8-10 mm; stainless steel) ZZ-11551 ZANDZ Clamp for connecting current collectors (D8-10 mm; stainless steel) 2
Grounding arrangement
7 ZANDZ galvanized steel bar (30 x 4 mm; bundle 6 m) ZZ-502-304-6 ZANDZ galvanized steel bar (30 x 4 mm; bundle 6 m) 3
8 ZANDZ clamp for connecting conductors (up to 40 mm) ZZ-005-064 ZANDZ clamp for connecting conductors (up to 40 mm) 4
9 ZANDZ clamp for a circular wire and a bar (D6-10 mm; up to 50 x 6; galvanized steel) ZZ-202-013 ZANDZ clamp for a circular wire and a bar (D6-10 mm; up to 50 x 6; galvanized steel) 2
10 ZANDZ copper-plated threaded grounding rod (D14; 1.5 m) ZZ-001-065 ZANDZ copper-plated threaded grounding rod (D14; 1.5 m) 6
11 ZANDZ threaded connecting coupling ZZ-002-061 ZANDZ threaded connecting coupling 4
12 ZANDZ takeoff tip ZZ-003-061 ZANDZ takeoff tip 3
13 ZANDZ guide head for jackhammer attachment ZZ-004-060 ZANDZ guide head for jackhammer attachment 2
14 ZANDZ conductive grease ZZ-006-000 ZANDZ conductive grease 1
15 ZANDZ waterproofing tape ZZ-007-030 ZANDZ waterproofing tape 2
16 ZANDZ attachment to the hammer (SDS max) ZZ-008-000 ZANDZ attachment to the hammer (SDS max) 1