High-rise catenary wire lightning protecton - is a system of external lightning protection, in which a wire acts as a lightning rod, suspended above the object to be protected on special supports which are located at some distance from this object.
High-rise catenary wire lightning protection has several advantages in comparison to the system of rod lightning rods:
- more effective; catenary-wire lightning protection system allows to achieve the so-called negative protection angles that greatly increases the reliability of protection and reduces the number of breakouts;
- to minimize the secondary effects of lightning on the object; at the correct placement of supports, lightning current spreading zone is outside the protected area;
- it allows not to mount additional constructions on the protected object; the system supports are placed outside the protected area;
- It is the home-grown technology; all elements are produced in Russia;
- has no analogues; the system of high-rise catenary-wire lightning protection ZANDZ is a unique complex offer considering the specifics of lightning protection of hazardous facilities (such as tank farms, oil storage tanks, etc.).

ZANDZ Опора системы тросовой молниезащиты с одним узлом крепления троса (высота подвеса 15 м)
Артикул: ZZ-204-115
(пр. Россия )
Опора выполнена из стали оцинкованной, 8-гранная, коническая. Ствол опоры в нижней части имеет фланец для крепления с фундаментом. В нижней части опора оснащена люком, который обеспечивает доступ к месту подключения заземляющего устройства. Люк закрывается крышкой, исключающей попадание атмосферных осадков и несанкционированное проникновение.
В комплект поставки входят:
- опора из граненой оцинкованной стали, 16 метров высотой;
- узел крепления троса сечением 50 мм2, размещенный на опоре на высоте 15 метров;
- анкерная закладная деталь фундамента.
Монтаж:
- на забетонированные фланцевые закладные детали фундамента;
- параметры фундамента определяются расчетом и зависят от зоны эксплуатации опор и параметров грунта;
Эксплуатационные характеристики
Климатическое исполнение и категория размещения (в соответствии с ГОСТ 15150-69) | УХЛ.1 |
Ветровой район в соответствии с СНиП 2.01.07-85 | до III |
Снеговой район по СНиП 2.01.07-85 | до V |
Предельная длина подвешиваемого троса | до 100 м |
Цена - 211 500,00 Руб. (под заказ)
ZANDZ Опора системы тросовой молниезащиты с одним узлом крепления троса (высота подвеса 20 м)
Артикул: ZZ-204-120
(пр. Россия )
Опора выполнена из стали оцинкованной, 8-гранная, коническая. Ствол опоры в нижней части имеет фланец для крепления с фундаментом. В нижней части опора оснащена люком, который обеспечивает доступ к месту подключения заземляющего устройства. Люк закрывается крышкой, исключающей попадание атмосферных осадков и несанкционированное проникновение.
В комплект поставки входят:
- опора из граненой оцинкованной стали, 21 метров высотой;
- узел крепления троса сечением 50 мм2, размещенный на опоре на высоте 20 метров;
- анкерная закладная деталь фундамента.
Монтаж:
- на забетонированные фланцевые закладные детали фундамента;
- параметры фундамента определяются расчетом и зависят от зоны эксплуатации опор и параметров грунта;
Эксплуатационные характеристики
ZANDZ System lsupportof catenary wire lightning protection with one node of wire fixation (suspension height - 35 m)
Product item:
The support is made of galvanized steel, 8-sided, conical. The support shank has flange in the bottom part for fixation with the foundation. At the bottom of the support it is equipped with a hatch that provides access to the place of connection of the grounding device. The hatch is closed with a cover, excluding insertion of precipitation and unauthorized entry.
The supply package includes:
- the support of faceted galvanized steel, 36.5 meters high;
- the mode of wire fixation with the section of 50 mm2placed on the support at the height of 35 meters;
- anchor embedded part of the foundation.
Installation:
- on concrete flanged embedded parts of the foundation;
- foundation parameters are determined by the calculation and depend on the area of operation of supports and soil parameters
Operating characteristics
Climatic modification and placement category (in accordance with GOST 15150-69) | GOST climatic modification.1 |
Wind region in accordance with SNiP 2.01.07-85 | to III |
Snowy region according to SNiP 2.01.07-85 | to V |
Limit length of the suspended wire | to 100 m |
Цена - 1 427 000,00 Руб. (под заказ)
ZANDZ system support of catenary wire lightning protection with two nodes of wire fixation (suspension height - 35 m)
Product item:
The support is made of galvanized steel, 8-sided, conical. The support shank has flange in the bottom part for fixation with the foundation. At the bottom of the support it is equipped with a hatch that provides access to the place of connection of the grounding device. The hatch is closed with a cover, excluding insertion of precipitation and unauthorized entry.
The supply package includes:
- the support of faceted galvanized steel, 36.5 meters high;
- two nodes for the wire fixation with cross- section of 50 mm2placed on the support at the height of 35 meters;
- anchor embedded part of the foundation
Installation:
- on concrete flanged embedded parts of the foundation;
- foundation parameters are determined by the calculation and depend on the area of operation of supports and soil parameters;
Operating characteristics
Climatic modification and placement category (in accordance with GOST 15150-69) | GOST climatic modification.1 |
Wind region in accordance with SNiP 2.01.07-85 | to III |
Снеговой район по СНиП 2.01.07-85 | до V |
Предельная длина подвешиваемого троса (на один узел) |
до 100 м |
Цена - 1 516 000,00 Руб. (под заказ)
ZANDZ galvanized steel ground wire
Product item:
Lightening protection wire accepts the lightning strike and take it away through the construction of supports into the grounding device.
ZZ-204-001 - is a spirally wire of galvanized steel cables, made in accordance with GOST 3063-80.
ZANDZ wire possesses high mechanical strength, has a low coefficient of expansion (to reduce the slack), and withstands and safely diverts lightning currents.
|
|
|
|
---|---|---|---|
ZANDZ ZZ-204-001 Galvanized steel ground wire | 50 | 9,1 |
Цена за метр - 158,00 Руб. (под заказ)

Grounding device
To organize the grounding device of the lightning protection system , you can choose one of our solutions:
- ZANDZ Modular grounding - standard solution for all soil types except rocky / ledge rock and permafrost;
- ZANDZ Electrolytic grounding it is used in the so-called "problematic" soils - with high resistivity (permafrost, rock, sand);
- Horizontal conductors made of copper-bonded steel serve to connect the grounding electrodes to each other and to connect them to the supports.
To choose a suitable system of catenary wire lightning protection and calculate the required grounding device, you ca always contact our Technical Centre.