Screened camera is a room for researches of bioelectric phenomena, the walla of which are shielding the chamber content (living organisms, units) from the affect of external electro-magnet fields. Resistance of the grounding device for such chambers should be 4 Ohm maximum. The ZANDZ Technical Center has recently received a request to calculate grounding for one of such screened chambers. Let's study the solution offered by our specialists.
Example of calculation of grounding for a screened chamber
Object: screened camera
Task: Carry out a grounding device with the resistance not exceeding 4 Ohms.
Solution:
Measures on provision of requirements to the grounding system of a screened camera:
1. Grounding is made in accordance with the EIC 7th ed.
2. Installation of 5 vertical electrodes 6 m long united by a horizontal electrode (copper-bonded tape 30x4 mm). The distance from the horizontal electrode to the object shaould be not less than 1 m, deepening 0.5 - 0.7 meters.
Grounding device calculation resistance:

The design resistance of the grounding device is 3,61 ohms.
Figure 1 shows the arrangement of equipment.
Chart 1 gives the list of the required equipment and materials for grounding of the screened chamber.

Figure 1 - Location of equipment for the screened chamber grounding.
Chart 1 - List of equipment and materials.
| № | Image | Product item | Product | Quantity, pcs. |
| 1. | ![]() |
ZZ-001-065 | ZANDZ Copper-coated threaded grounding rod (D14; 1.5 m) | 20 |
| 2. | ![]() |
ZZ-002-061 | ZANDZ Threaded coupler | 16 |
| 3. | ![]() |
ZZ-003-061 | ZANDZ Starting tip | 5 |
| 4. | ![]() |
ZZ-004-060 | ZANDZ Driving head for a jackhammer | 4 |
| 5. | ![]() |
ZZ-006-000 | ZANDZ Conductive grease | 2 |
| 6. | ![]() |
ZZ-008-000 | ZANDZ Header for a jackhammer (SDS max) | 1 |
| 7. | ![]() |
ZZ-005-064 | ZANDZ Clamp for connecting conductors (up to 40 mm) | 7 |
| 8. | ![]() |
ZZ-007-030 | ZANDZ Waterproof tape | 2 |
| 9. | ![]() |
GL-11075-20 | GALMAR Copper-bonded tape (30 * 4 mm / S 120 mm²; coil of 20 meters) | 1 |
| 10 | ![]() |
GL-11075-10 | GALMAR Copper-bonded tape (30 * 4 mm / S 120 mm²; coil of 10 meters) | 1 |
| 11. | ![]() |
ZZ-500-110 | ZANDZ Grounding conductor (10m; S25, single-core, with a tip for the bolt D8) | 1 |
Do you have any questions on grounding of screened chambers? Please contact our ZANDZ Technical center!
See also: