LIGHTNING PROTECTION OF A BLOCK-MODULE FOR STORAGE OF A FIRE-FIGHTNING TANK IN OSIPOVICH DISTRICT

A fire-fighting tank is a wonderful helper for large fires. In idle mode, it is stored in a block-module which performs as a garage. When building this block-module for a fire-fighting tank, it is necessary to make lightning protection system.

Lightning protection of a block-module for storage of a fire-fightning tank

ZANDZ Technical Center accepted an inquiry for the calculation of lightning protection systems and grounding of a block-module for storing a fire-fighting tank. The task solution was as follows:

Initial data:

  • sizes (l/w/h): 12,7 m х 6m х 7m;
  • soil resistivity: 100 Ohm * m

 

Task:

Calculate external lightning protection system and grounding.

 

The set of measures to provide the required lightning protection for a block-module for storing a fire-fighting tank is offered by the following solutions:

  • installation of two lightning rods 5 meters high at the edges of the roof. Distance between the strut palms - up to 1 m (see fig.1); connection of the down conductor is performed with the help of clamp ZZ-202-002;
  • lightning rods are united with the help of steel copper-bonded wire d8 mm for the organization of not less than 2 down conductors;
  • fixation of down conductors is carried out with the help of clamps GL-11747A on the roof, GL-11703A on vertical surfaces.
  • installation of the grounding device according to AD, item 2.26 consisting of 2 vertical electrodes 3 m long, united by the horizontal electrode (copper-bonded tape 30x4 mm). The distance from the horizontal electrode to the object should be not less than 1 m, deepening 0.5 - 0.7 meters.

Grounding device resistance calculation:

The design resistance of the grounding device is 9.16 Ohms, which is less than the required one of 10 Ohm.

 

Results of calculations for the protection zone in compliance with the IS:

Air terminal mast № 1,2 (ZZ-201-005):

h = 11 m;

Height of the cone according to the IS chart. 3.4

The radius of the cone according to the IS chart. 3.4:

Distance between the lightning rods:

L=13 m;

The ultimate distance between the lightning rods, according to the IS chart 3.6:

There is no vertical clearance.

 

Location of equipment and protection zone are shown in figure 1.

The list of equipment and required materials is given in Table 1.

Lightning protection of a block-module for storage of a fire-fightning tank

Figure 1 - Location of equipment.

 

Table 1 - Materials requirement list.

№ Figure Product item Name Quantity, pcs.
1. ZANDZ Vertical air-terminal -mast 5 m (stainless steel) ZZ-201-005 ZANDZ Vertical air-terminal -mast 5 m (stainless steel) 2
2. ZANDZ Fastening for lightning rod to the wall (stainless steel) ZZ-203-001 ZANDZ Fastening for lightning rod to the wall (stainless steel) 2
3. ZANDZ Clamp to the lightning rod D42 mm for down conductors (stainless steel) ZZ-202-002 ZANDZ Clamp to the lightning rod D42 mm for down conductors (stainless steel) 2
4. GALMAR Copper-bonded wire (D 8mm / S 50 mm²; coil of 50 meters) GL-11149-50 GALMAR Copper-bonded wire (D 8mm / S 50 mm²; coil of 50 meters) 1
5. GALMAR Clamp for connecting down conductors (painted galvanized steel) GL-11551A GALMAR Clamp for connecting down conductors (painted galvanized steel) 2
6. GALMAR Clamp for the roof covered with metal profiles / corrugated sheets, for down conductor (painted galvanized steel) GL-11747A GALMAR Clamp for the roof covered with metal profiles / corrugated sheets, for down conductor (painted galvanized steel) 30
7. GALMAR Clamp to the facade for down conductor with its elevation above the clamp to 15 mm (painted galvanized steel) GL-11703A GALMAR Clamp to the facade for down conductor with its elevation above the clamp to 15 mm (painted galvanized steel) 20
8. ZANDZ Copper-bonded threaded grounding rod (D14; 1.5 m) ZZ-001-065 ZANDZ Copper-bonded threaded grounding rod (D14; 1.5 m) 4
9. ZANDZ Threaded coupler ZZ-002-061 ZANDZ Threaded coupler 3
10. ZANDZ Starting tip ZZ-003-061 ZANDZ Starting tip 2
11. ZANDZ Driving head for a jackhammer ZZ-004-060 ZANDZ Driving head for a jackhammer 1
12. ZANDZ Conductive grease ZZ-006-000 ZANDZ Conductive grease 1
13. ZANDZ Header for a jackhammer (SDS max) ZZ-008-000 ZANDZ Header for a jackhammer (SDS max) 1
14. ZANDZ Clamp for connecting conductors (up to 40 mm) ZZ-005-064 ZANDZ Clamp for connecting conductors (up to 40 mm) 4
15. ZANDZ Waterproof tape ZZ-007-030 ZANDZ Waterproof tape 1
16. GALMAR Copper-bonded tape (30 * 4 mm / S 120 mm²; coil of 20 meters) GL-11075-20 GALMAR Copper-bonded tape (30 * 4 mm / S 120 mm²; coil of 20 meters) 1