The ZANDZ Technical Center received a request for the calculation of an external lightning protection system and grounding of the courthouse in Yakutia. Let us consider the solution that was proposed by our experts.
Source data:
- architectural drawings;
- soil resistivity - 1000 Ohm * m..
Task:
- calculate external lightning protection system;
- calculate a grounding device with the resistance of not more than 40 Ohm.
Solution:
Lightning protection and grounding of the industrial building are made in accordance with:
-
IS 153-34.21.122-2003 "Instructions for lightning protection of buildings, structures and industrial communications", hereinafter IS;
-
AD 34.21.122-87 "Instruction on arrangement of lightning protection of buildings and structures", hereinafter AD/
The object refers to III category of lightning protection in accordance with AD and to "ordinary" in accordance with IS.
A set of measures to ensure the necessary requirements for a lightning protection system and the grounding device of a multifunctional complex is represented by the following solutions:
- Lightning protection is carried out with the help of a lightning mesh with a distance between the cells of not more than 10 m. The mesh is made of steel copper-bonded wire (the tickness of the copper coating is not less than 70 mcm), the diameter of the wire is d8 mm (GL-11149).
- Steel copper-bonded wire d8 mm (GL-11149) is used as a down conductor (thickness of the copper bonding at least 70 mcm).
- Installation of down conductors is carried out with the help of clamp GL-11711 - on a flat roof, GL-11703A -on vertical surfaces. Distance between the clamps- from 0.8 up to 1.0 meter.
- A universal clamp GL-11551A is used for connecting the mill products along the length and in the nods.
- All metal elements, placed on the roof must be connected to the down conductor with the help of clamps GL-11545A. Stairs and hand railings are connected with the help of a clamp-bridge GL-11514N.
- Down conductors are connected by horizontal belts near the ground and every 20 m along the height of the building, according to IS 153-34.21.122-2003, clause 3.2.2.3.
- Copper-bonded steel electrodes 3 m long are used in places of downdrops as vertical ground electrodes. Copper-bonded steel tape with the cross-section of 30x4 mm uniting all vertical electrodes is used as a horizontal ground electrode. The distance to the object foundation- not less than 1 m. Deepening of the tape 0,5-0,7 m.
- In accordance with the EIC-7 ed., P.1.7.55 - Grounding devices for protective grounding of electrical installations of buildings and structures and lightning protection of the 2nd and 3rd categories of these buildings and structures, as a rule, should be common.
- The calculated value of the resistance of the grounding device is 15.27 Ohms.
- If there are metal reinforce concrete framings, they must be connected to down conductors/ grounding device.
- Connection to the grounding device is carried out with the help of clamps ZZ-005-064.
The resistance calculation of the grounding device:
Vertical electrode resistance:
where ρэкв - equivalent soil resistivity - 1000 Ohm*m;
L - vertical electrode length - 3 m;
d- vertical electrode diameter - 0.014 m;
T- deepening - the distance from the ground surface to the ground electrode system - 2 m;
where t is the deepening of the electrode top - 0,5 m
Horizontal electrode resistance:
whereρ - equivalent soil resistivity - 1000 Ohm*m;
b - width of the horizontal electrode - 0.03 m;
h - horizontal electrode laying depth -0.5 m;
Lгор - horizontal electrode length - 165 m.
Impedance of the grounding device:
where n - number of kits, vertical ground electrodes -9 pc., horizontal ground electrode - 1 pc. ;
Kисп - utilization ratio, 0.69.
The design resistance of the grounding device is 15,27 ohms, which is less than the required value of 40 ohms.
Figure 1 shows the arrangement of equipment.
Figure 1 - Location of equipment.
The list of required material is given in Table 1.
Table 1 - List of materials needs.
№ | Product item | Name | Quantity, pcs. | Mass, kg. | Note |
1. | GL-11149-50 | GALMAR Copper-bonded wire (D 8mm / S 50 mm²; coil of 50 meters) | 25 | 0,41 | Weight per meter |
2. | GL-11545A | GALMAR Clamp on the gutter for a down conductor (painted galvanized steel) | 20 | 0,112 | |
3. | GL-11551A | GALMAR Clamp for connecting down conductors (painted galvanized steel) | 200 | 0,07 | |
4. | GL-11711 | GALMAR Clamp on a flat roof for the down conductor (plastic, concrete) | 220 | 1 - 1,2 | |
5. | GL-11703A | GALMAR Clamp to the facade for down conductor with its elevation above the clamp to 15 mm (painted galvanized steel) | 1300 | 0,02 | |
6. | GL-11514N | GALMAR clamp to the rainwater downpipe for a down conductor (tape of tinned copper + stainless steel clamp) | 20 | 0,076 | |
7. | GL-11075-50 | GALMAR Copper-bonded tape (30 * 4 mm / S 120 mm²; coil 50 meters) | 4 | 0,98 | Вес за метр |
8. | ZZ-001-065 | ZANDZ Copper-bonded threaded grounding rod (D14; 1.5 m) | 18 | 2,00 | |
9. | ZZ-002-061 | ZANDZ Threaded coupler | 10 | 0,08 | |
10. | ZZ-003-061 | ZANDZ Starting tip | 9 | 0,07 | |
11. | ZZ-004-060 | ZANDZ Driving head for jackhammer | 4 | 0,09 | |
12. | ZZ-005-064 | ZANDZ Clamp for connecting conductors (up to 40 mm) | 25 | 0,16 | |
13. | ZZ-006-000 | ZANDZ Conductive grease | 1 | 0,10 | |
14. | ZZ-007-030 | ZANDZ Waterproof tape | 9 | 0,40 | |
15. | ZZ-008-000 | ZANDZ Header for a jackhammer (SDS max) | 1 | 0,50 |