How to perform lightning protection of a hotel?

A large hotel is most often a building of several structures with the height of more than 50 m. Usually, such tall buildings actively attract lightning.

 Hotel Lightning Protection

The hotel can simultaneously accommodate hundreds of guests. In order to protect them from fire and other dangerous effects of atmospheric discharges, a reliable lightning protection system should be put into the project of the hotel. Let's study the solution that the engineers of the ZANDZ Technical Center offered for one of the hotels.

Task

To make the choice of the lightning rods necessary for lightning protection of a hotel. The building under protection is an ordinary structure in terms of lightning protection in accordance with the IS and is in Category 3 according to the AD.

The solution to lightning protection of hotels

The calculations are made in accordance with the following documents:

Protection of buildings from lightning strikes is carried out with the help of lightning rods. A lightning rod is a device rising above the facility that diverts lightning current into the ground without entering the facility. It consists of a lightning rod which directly takes the lightning discharge upon itself, a down conductor and a ground electrode.

Lightning protection system description

Measures to ensure compliance with the requirements for hotel lightning protection system:

  1. Installation of 3 rods 7 m high, fixed to the wall. It is taken into account that 1 m of the lightning rods height is used for fixation.
  2. Installation of 2 rods 4 m high, fixed to the wall. It is taken into account that 0.7 m of the lightning rods height is used for fixation.

Location of the lightning rods at the hotel is shown in Figure 1. You can see protection zone B of the AD.

Calculation of reliability of lightning protection of the hotel when calculating the probability of a lightning strike to an object

The following source data are taken for the calculation:

The density of lightning strikes into the ground - 4 strikes / sq. km per year.

The results of lightning protection calculation performed by the software, developed by OJSC "Energy Institute to the name of Krzhizhanovsky" (OJSC" ENIN ") are given in table 1.

Table 1 - Results of lightning protection calculation

Object

Lightning rod height, m

Protection reliability

Number of strikes into an object,

year-1

Number of breakthroughs into the object,

year-1

Period of srikes, year

Period of breakthroughs, year

1

Hotel

7 and 4 m

0,944

0,3

0,017

once in 3 years

once in 59 years

 

Hotel lightning protection scheme

Figure 2. Lightning rods location planв

Components for the hotel's external lightning protection system

Fig.

Product item

Product

Quantity

Lightning protection system

1. ZZ-201-007-3 ZANDZ Vertical air-terminal mast 7 m high with a set of 2 fastenings to the wall (stainless steel) 3
2. ZZ-202-002 ZANDZ Clamp to the lightning rod D42 mm for down conductors (stainless steel) 3
3. ZZ-201-004 ZANDZ Vertical air-terminal -mast 4 m (stainless steel) 2
4. ZZ-203-001 ZANDZ Fastening for lightning rod to the wall (stainless steel) 2
5. GL-20022 GALMAR Clamp to lightning rods for down conductors (stainless steel) 2

 

Do you have any questions about hotel lightning protection? Please contact our ZANDZ Technical center!