Grounding devices for the protection of medical equipment - tomographs, x-ray machines and other highly sensitive equipment - should provide low resistance. The documents for such equipment often indicate that the required resistance for it should not exceed 2 ohms. The ZANDZ Technical Center recently received a request to achieve this level for one of the hospitals. We proposed to use a large number of grounding electrodes with a length of 6 m. Let's study this solution in more detail.
Calculation example of grounding for the hospital medical equipment
Object: Hospital in Moscow.
Task:
Perform a grounding device for the hospital, providing the resistance of not more than 2 ohms
Solution:
A set of measures to ensure the necessary requirements for the grounding system of the hospital medical equipment:
1. Grounding is made in accordance with the EIC 7th ed.
2. Installation of a grounding device consisting of 10 vertical electrodes 6 m long united by a horizontal electrode (copper-bonded tape 30x4 mm). The distance from the horizontal electrode to the facility shall not be less than 1 m, deepening 0.5 - 0.7 meters.
Hospital's grounding device resistance calculation:

The design resistance of the grounding device is 1,96 Ohm..
Figure 1 shows the arrangement of equipment.
Table 1 gives the list of the required equipment and materials.
Location of equipment for hospital grounding.Подключить к главной заземляющей шине – connect to the main grounding bus
Электрод - electrode
Полоса омедненная 30 на 4 – copper-bonded tape 30 to 4
Table 1 - List of equipment and materials for hospital grounding.
| № | Fig. | Product item | Name | Quantity, pcs |
| 1. | ![]() |
ZZ-001-065 | ZANDZ Copper-coated threaded grounding rod (D14; 1.5 m) | 40 |
| 2. | ![]() |
ZZ-002-061 | ZANDZ Threaded coupler | 31 |
| 3. | ![]() |
ZZ-003-061 | ZANDZ Starting tip | 10 |
| 4. | ![]() |
ZZ-004-060 | ZANDZ Driving head for a jackhammer | 8 |
| 5. | ![]() |
ZZ-006-000 | ZANDZ Conductive grease | 4 |
| 6. | ![]() |
ZZ-008-000 | ZANDZ Header for a jackhammer (SDS max) | 1 |
| 7. | ![]() |
ZZ-005-064 | ZANDZ Clamp for connecting conductors (up to 40 mm) | 14 |
| 8. | ![]() |
ZZ-007-030 | ZANDZ Waterproof tape | 4 |
| 9. | ![]() |
GL-11075-50 | GALMAR Copper-bonded tape (30 * 4 mm / S 120 mm²; coil of 50 meters) | 1 |
| 10. | ![]() |
GL-11075-20 | GALMAR Copper-bonded tape (30 * 4 mm / S 120 mm²; coil of 20 meters) | 2 |
Any questions about hospital grounding? Please contact our ZANDZ Technical center!!
Related Articles: