GROUNDING AND LIGHTNING PROTECTION OF AN ASPHALT-CONCRETE FACTORY IN THE CRIMEA

GROUNDING AND LIGHTNING PROTECTION OF AN ASPHALT-CONCRETE FACTORY IN THE CRIMEA

Asphalt-concrete factory buildings are metal structures which can be used as natural lightning rods. But sometimes customers require to protect all equipment located on the territory by free standing lightning rods. ZANDZ Technical center has recently recieved such a task. Let's consider what solution was offered by our specialists.

 

Calculation example of an asphalt-concrete factory lightning protection

 

Object: asphalt-concrete factory

Figure 1 - Object plan

Figure 1 - Object plan

 

Task: Perform lightning protection and grounding system calculations for the asphalt-concrete factory.

 

Protection of buildings and structures against lightning discharges is ensured by lightning rods. A lightning rod is a device rising above the facility that diverts lightning current into the ground without entering the facility. It consists of a lightning rod which directly takes the lightning discharge upon itself, a down conductor and a ground electrode.

Solutions to meet the requirements for a lightning protection system:

1. Lightning protection is carried out in accordance with IS 153-34.21.122-2003., "Instructions for lightning protection of buildings, structures and industrial communications" (hereinafter IS) and AD 34.21.122-87 "Instructions for lightning protection of buildings and structures" (hereinafter AD).

2. The object refers to category 3 of lightning protection. System reliability must be not less than 0,9.

3. The lightning protection of the object is made with the help of 3 vertical detached air-terminal masts 5,7 m high (GL-21105G).

4. Installation of down conductors is carried out with the help of clamp GL-11703A on vertical surfaces. Distance between the clamps- from 0.8 up to 1.0 meter.

5. To connect rolled metal over the length and in the mesh nodes, a universal clamp GL-11551A is used.

6. All metal elements, placed on the roof must be connected to lightning protection mesh with the help of clamps GL-11545A. Stairs, railing are connected with the help of GL-11514 clamp.

7. Installation of a grounding device for each lightning rod, consisting of 2 vertical electrodes 3 m long, connected by a horizontal electrode (copper bonded tape of 30x4 mm) not less than 5 m long. The distance from the horizontal electrode to the object is not less 1 m, deepening 0,5-0,7 m;

8. In case of presence of the existing grounding device, they should be united into one grounding device in accordance with EIC p.1.7.55.

 

Calculation of protection zone in accordance with AD:

Lightning rod № 1, 2 (GL-21105G):

Lightning rod № 1, 2 (GL-21105G)

Air terminal mast № 1, 3 (GL-21105G):

Air terminal mast № 1, 3 (GL-21105G)

 

Grounding device calculation resistance:

 

The design resistance of the grounding device is 2,54 Ohm.

 

Figure 2 shows the arrangement of equipment.

Table 1 gives the list of the required equipment and materials.

Lightning protection of an asphalt concrete plant in Crimea

Figure 2- Arrangement of equipment for grounding and lightning protection on an asphalt-concrete factory

 

Chart 1 - List of need in materials.

№ Fig. Product item Product Quantity, pcs.
1. GL-21105G GALMAR Vertical lightning rod (air terminal-mast) (5.7 meters) 3
2. GL-20023 GALMAR Clamp to the air-terminal mast - GL-21104G / GL-21105G for down conductors (stainless steel) 3
3. ZZ-203-001

ZANDZ Fastening for lightning rod to the wall  (stainless steel)

 
3
4. GL-11149-50 GALMAR Copper-coated wire (D 8mm / S 50 mm²; coil of 50 meters) 2
5. GL-11703A GALMAR Clamp to the facade for down conductor with its elevation above the clamp to 15 mm (painted galvanized steel) 100
6. GL-11551A GALMAR Clamp for connecting down conductors (painted galvanized steel) 2
7. GL-11545A GALMAR Clamp on the gutter for a down conductor (painted galvanized steel) 10
8. GL-11514 GALMAR Clamp-bridge on a gutter for down conductor (tinned copper) 30
9. GL-11562A GALMAR Control clamp for connecting down conductors, wire + tape (painted galvanized steel) 6
10. ZZ-001-065 ZANDZ Copper-coated threaded grounding rod (D14; 1.5 m) 12
11. ZZ-002-061 ZANDZ Threaded coupler 7
12. ZZ-003-061 ZANDZ Starting tip 6
13. ZZ-004-060 ZANDZ Driving head for a jackhammer 3
14. ZZ-006-000 ZANDZ Conductive grease 1
15. ZZ-008-000 ZANDZ Header for a jackhammer (SDS max) 1
16. ZZ-005-064 ZANDZ Clamp for connecting conductors (up to 40 mm) 8
17. ZZ-007-030 ZANDZ Waterproof tape 2
18. GL-11075-10 GALMAR Copper-bonded tape (30 * 4 mm / S 120 mm²; coil of 10 meters) 3

 