FUNCTIONAL GROUNDING OF ELECTRIC INSTALLATIONS

Any high-technology equipment at the place of production or in some workshop requires a special attitude. In particular, good grounding and potential equalization system are required, which will allow the use of equipment, as they say, to the maximum.

FUNCTIONAL GROUNDING OF ELECTRIC INSTALLATIONS

The ZANDZ Technical Center received a request for the calculation of a functional grounding system for electrical installations (machines) at the place of production. Let's consider what solution was offered by our technical experts.
 
Initial data:
The soil resistivity adopted for calculations based on the data provided is 300 Ohm * m.
 
Task:
It is necessary to calculate the functional grounding with the resisance of not more than 4 Ohm.
 
The set of measures on the provision of the necessary requirements to the grounding device is presented by the following solutions:
Installation of 21 vertical electrodes D = 14.2 mm, L = 6 m, the electrodes are combined with a copper-bonded steel tape with the cross-section of 30x4 mm. Laying depth of 0.5 m - 0.7 m. Burial depth of 0.5 m - 0.7 m.
 
Grounding device resistance calculation:
The design resistance of the grounding device is 3,8 ohms, which is less than the required value of 4 ohms.
 

The layout of the equipment is shown in Fig.1.

The list of required material is given in Table 1.

functional grounding of electrical installations

Электрод - electrode
Полоса стальная оцинкованная сечением – steel galvanized tape with the cross-section of 30*4 mm

Figure 1 - Grounding device elements layout.
 
Table 1 - List of material needs.

№ Figure Product item Name Quantity, pcs.
1. ZZ-001-065 ZANDZ Copper-bonded threaded grounding rod (D14; 1.5 m) 84
2. ZZ-002-061 ZANDZ Threaded coupler 64
3. ZZ-003-061 ZANDZ Starting tip 21
4. ZZ-004-060 ZANDZ Driving head for a jackhammer 17
5. ZZ-008-000 ZANDZ Header for a jackhammer (SDS max) 1
6. ZZ-005-064 ZANDZ Clamp for connecting conductor (up to 40 mm) 25
7. ZZ-007-030 ZANDZ Waterproof tape 7
8. ZZ-006-000 ZANDZ Conductive grease 7
9. GL-11075-50 GALMAR Copper-bonded tape (30 * 4 mm / S 120 mm²; coil of 50 meters) 2
10. GL-11075-20 GALMAR Copper-bonded tape (30 * 4 mm / S 120 mm²; coil of 20 meters) 1

 Do you have questions or do you need to calculate functional grounding for electrical installations at the production? Send your request to info@zandz.ru.

 