Functional (technological) grounding for a hospital is made coming out of requirements in the technical passport for equipment. The ZANDZ Technical Center recently received a request to achieve the resistance of not more than 2 Ohm. We will study our solution in detail.
Example of calculation of a hospital functional grounding
Object: hospital
Task:
Perform a grounding device for the hospital, providing the resistance of not more than 2 ohms.
Solution:
A set of measures to ensure the necessary requirements to the functional grounding system of the hospital:
- Grounding is made in accordance with the EIC 7th ed.
- Installation of a grounding device consisting of 11 vertical electrodes 6 m long united by a horizontal electrode (copper-bonded tape 30x4 mm). The distance from the horizontal electrode to the object should be not less than 1 m, deepening 0.5 - 0.7 meters.
Hospital's grounding device resistance calculation:
The design resistance of the grounding device is 1,95 Ohm.
Figure 1 shows the arrangement of equipment.
Table 1 gives the list of the required equipment and materials.
Figure 1 - Location of equipment for hospital functional grounding.
Электрод- Electrode L = 6m, D=14mm
Полоса омедненная – Copper-bonded tape 30 x 4mm
Table 1 - List of equipment and materials for hospital grounding.
№ | Image | Product item | Product | Quantity, pcs. |
1. | ZZ-001-065 | ZANDZ Copper-bonded threaded grounding rod (D14; 1.5 m) | 44 | |
2. | ZZ-002-061 | ZANDZ Threaded coupler | 34 | |
3. | ZZ-003-061 | ZANDZ Starting tip | 11 | |
4. | ZZ-004-060 | ZANDZ Driving head for a jackhammer | 9 | |
5. | ZZ-006-000 | ZANDZ Conductive grease | 4 | |
6. | ZZ-008-000 | ZANDZ Header for a jackhammer (SDS max) | 1 | |
7. | ZZ-005-064 | ZANDZ Clamp for connecting conductor (up to 40 mm) | 13 | |
8. | ZZ-007-030 | ZANDZ Waterproof tape | 4 | |
9. | GL-11075-50 | GALMAR Copper-bonded tape (30 * 4 mm / S 120 mm²; coil of 50 meters) | 2 | |
10. | ZZ-500-110 | ZANDZ Grounding conductor (10m; S25, single-core, with a tip for the bolt D8) | 1 |
Any questions about hospital functional grounding? Please contact our ZANDZ Technical center!
See also: