The ZANDZ Technical Center received a request to calculate the working grounding for the electric laboratory. Further we will consider what our engineers have offered!
Initial data:
- specific resistance of the soil used for calculations – 100 Ohm * m;
- the available area for the installation of the grounding device is 30x30 m.
Task:
It is necessary to calculate the working grounding device with a resistance of not more than 0.5 ohms.
The set of measures to provide the required lightning protection is offered by the following solutions:
- Installation of a grounding device, consisting of a grounding mesh with a pitch of 3x3 m using a copper-bonded tape with the cross section of 30x4 mm, and vertical electrodes 3 m long, in knots (106 pcs.). The burial depth is 0.5 – 0.7 meters.
Grounding device resistance calculation:

The design resistance of the grounding device is 0,49 Ohm, which is less than the required value of 0,5 ohms.
Конструкция заземляющего устройства показана на рис.1
Figure 1 - Location of equipment.
Вертикальный электрод – vertical electrode
Полоса омедненная – copper-bonded tape
The list of required material is given in Table 1.
Table 1 - Materials requirement list.
| № | Fig. | Product item | Name | Quantity, pcs. |
| 1. | ![]() |
ZZ-001-065 | ZANDZ Copper-bonded threaded grounding rod (D14; 1.5 m) | 212 |
| 2. | ![]() |
ZZ-002-061 | ZANDZ Threaded coupler | 107 |
| 3. | ![]() |
ZZ-003-061 | ZANDZ Starting tip | 106 |
| 4. | ![]() |
ZZ-004-060 | ZANDZ Driving head for a jackhammer | 43 |
| 5. | ![]() |
ZZ-006-000 | ZANDZ Conductive grease | 11 |
| 6. | ![]() |
ZZ-008-000 | ZANDZ Header for a jackhammer (SDS max) | 2 |
| 7. | ![]() |
ZZ-005-064 | ZANDZ Clamp for connecting conductor (up to 40 mm) | 118 |
| 8. | ![]() |
ZZ-007-030 | ZANDZ Waterproof tape | 29 |
| 9. | ![]() |
GL-11075-50 | GALMAR Copper-bonded tape (30 * 4 mm / S 120 mm²; coil of 50 meters) | 12 |
Do you have questions or do you need to calculate the working grounding for the electric laboratory? Send your request to info@zandz.ru.