Lightning Protection and Grounding of a Solar Power Plant in the Krasnodar Kray

The ZANDZ Technical Center has received a request to calculate the lightning protection system for a solar power plant. Let us further consider a solution proposed by our specialists.

Lightning protection and grounding for a solar power plant in the Krasnodar Kray

Initial data:

  • facility: solar power plant;

  • dimensions: 120 m x 102 m x 2 m;

  • Soil resistivity: 100 Ohm*m.

 

Task:

  • calculate the lightning protection system;

  • calculate the grounding device.

 

Solution:

Lightning protection and grounding of the building are made in accordance with:

 

The facility is classified as “conventional” from the viewpoint of SO and as Category III of the lightning protection according to RD.

 

A set of measures to provide necessary requirements to the lightning protection system and to the grounding arrangement for the solar power plant includes the following solutions:

  1. 10 m lightning arresters located along the perimeter of the protected area are used as lightning arresters to protect the area.

  2. Copper-plated steel electrodes 3 m long are used as a vertical grounding arrangement.

  3. The copper-plated steel strip with a cross-section of 30 x 4 mm, combining all vertical electrodes, is used as a horizontal ground electrode. The distance to the mast foundation is at least 1 m. Strip deepening is 0.5 to 0.7 m.

  4. Connection to the grounding arrangement is made through clamps ZZ-005-064.

 

The results of calculation of protection zones according to SO:

h = 10 m;

Cone height according to SO, Table 3.4:

h0 = 0,85*h = 8,5 m;

Cone radius according to SO, Table 3.4:

r0 = 1,2*h = 12 m;

For the protection zone with the required reliability, radius rx at the height of h0 = 2 m is defined as:

Protection radius at the predetermined height

М - m

Distance between the lightning arresters (maximum):

L = 38 m;

Limit distance between lightning arresters according to SO, Table 3.6:

Limit distances between lightning arresters

Sagging height:

Slag height of the protection zone

For the protection zone with the required reliability, radius rcx at height h0 = 2 m is defined as follows:

Protection zone radius at the predetermined height between the masts

 

Ground terminal resistance calculation:

Vertical electrode resistance:

Calculation of a vertical grounding electrode

Ом - Ohm
Верт - Vert
Экв - Eq

where    ρρeq is equivalent soil resistivity, 100 Ohm·m;

L – is vertical electrode length, 3 m;

d – is vertical electrode diameter, 0.014 m;

T – deepening - is the distance from the ground surface to the ground electrode, 2 m;

Grounding electrode depth

where     t  – is deepening of the top of the electrode, 0.5 m.

 

Horizontal electrode resistance:

Calculation of a horizontal grounding electrode

Ом - Ohm
Гор - Hor

where    ρ – is soil resistivity, 100 Ohm·m;

b - is horizontal electrode width, 0.03 m;

h - is horizontal electrode depth, 0.7 m;

Lhor - is horizontal electrode length, 1,160 m.

 

Electrical impedance of the grounding arrangement:

Impedance of a grounding arrangement

Ом - Ohm
ЗУ - GA

where n – is a number of sets, vertical grounding arrangements - 11 pcs, horizontal grounding arrangement - 1 pc;

Kutil is utilization rate, 0.63.

 

The calculated resistance of the grounding arrangement is 0,38 Ohm.

 

The location of the equipment is shown in Figure 1

.Lightning protection and grounding of a solar power plant in the Krasnodar Kray

Условные обозначения - Legend
- молниеприемник-мачта высотой 10 м - 10 m lightning rod
- полоса стальная оцинкованная сечением 30х4 мм - steel zinc-plated bar with cross-section 30 x 4 mm
- зажим для подключения проводника - clamp for connecting conductor
- вертикальный заземлитель длиной 3 м - 3 m vertical grounding electrode
- зона защиты на высоте 2 м - protection zone at the height 2 m

Figure 1. Equipment layout.

 

The list of necessary materials is given in Table 1.

 

Table 1. List of needed materials.

№ Part number Name Quantity, pcs. Unit weight, kg Note
LIGHTNING PROTECTION:
1. ZZ-201-010 ZANDZ 10 m vertical lightning arrester (zinc-plated steel; with parts embedded under the foundation) 1    
GROUNDING ARRANGEMENT:
2. GL-11075-50 GALMAR Copper-plated strip (30 * 4 mm / S 120 mm²; 50-meter strip bundle) 26 0,98 Вес за метр
3. ZZ-001-065 ZANDZ Copper-plated threaded grounding rod (D14; 1,5 m) 22 2,00  
4. ZZ-002-061 ZANDZ Threaded coupling 12 0,08  
5. ZZ-003-061 ZANDZ Termination 11 0,07  
6. ZZ-004-060 ZANDZ Guide head for jackhammer attachment 5 0,09  
7. ZZ-005-064 ZANDZ Conductor connection terminal (up to 40 mm) 106 0,312  
8. ZZ-006-000 ZANDZ Conductive grease 2 0,10  
9. ZZ-007-030 ZANDZ Waterproofing tape 36 0,40  
10. ZZ-008-000 ZANDZ Attachment to the hammer (SDS max) 1 0,50  