Lightning Protection and Grounding of a Solar Power Plant in the Krasnodar Kray

The ZANDZ Technical Center has received a request to calculate the lightning protection system for a solar power plant. Let us further consider a solution proposed by our specialists.

Lightning protection and grounding for a solar power plant in the Krasnodar Kray

Initial data:

  • facility: solar power plant;

  • dimensions: 120 m x 102 m x 2 m;

  • Soil resistivity: 100 Ohm*m.

 

Task:

  • calculate the lightning protection system;

  • calculate the grounding device.

 

Solution:

Lightning protection and grounding of the building are made in accordance with:

 

The facility is classified as “conventional” from the viewpoint of SO and as Category III of the lightning protection according to RD.

 

A set of measures to provide necessary requirements to the lightning protection system and to the grounding arrangement for the solar power plant includes the following solutions:

  1. 10 m lightning arresters located along the perimeter of the protected area are used as lightning arresters to protect the area.

  2. Copper-plated steel electrodes 3 m long are used as a vertical grounding arrangement.

  3. The copper-plated steel strip with a cross-section of 30 x 4 mm, combining all vertical electrodes, is used as a horizontal ground electrode. The distance to the mast foundation is at least 1 m. Strip deepening is 0.5 to 0.7 m.

  4. Connection to the grounding arrangement is made through clamps ZZ-005-064.

 

The results of calculation of protection zones according to SO:

h = 10 m;

Cone height according to SO, Table 3.4:

h0 = 0,85*h = 8,5 m;

Cone radius according to SO, Table 3.4:

r0 = 1,2*h = 12 m;

For the protection zone with the required reliability, radius rx at the height of h0 = 2 m is defined as:

Protection radius at the predetermined height

М - m

Distance between the lightning arresters (maximum):

L = 38 m;

Limit distance between lightning arresters according to SO, Table 3.6:

Limit distances between lightning arresters

Sagging height:

Slag height of the protection zone

For the protection zone with the required reliability, radius rcx at height h0 = 2 m is defined as follows:

Protection zone radius at the predetermined height between the masts

 

Ground terminal resistance calculation:

Vertical electrode resistance:

Calculation of a vertical grounding electrode

Ом - Ohm
Верт - Vert
Экв - Eq

where    ρρeq is equivalent soil resistivity, 100 Ohm·m;

L – is vertical electrode length, 3 m;

d – is vertical electrode diameter, 0.014 m;

T – deepening - is the distance from the ground surface to the ground electrode, 2 m;

Grounding electrode depth

where     t  – is deepening of the top of the electrode, 0.5 m.

 

Horizontal electrode resistance:

Calculation of a horizontal grounding electrode

Ом - Ohm
Гор - Hor

where    ρ – is soil resistivity, 100 Ohm·m;

b - is horizontal electrode width, 0.03 m;

h - is horizontal electrode depth, 0.7 m;

Lhor - is horizontal electrode length, 1,160 m.

 

Electrical impedance of the grounding arrangement:

Impedance of a grounding arrangement

Ом - Ohm
ЗУ - GA

where n – is a number of sets, vertical grounding arrangements - 11 pcs, horizontal grounding arrangement - 1 pc;

Kutil is utilization rate, 0.63.

 

The calculated resistance of the grounding arrangement is 0,38 Ohm.

 

The location of the equipment is shown in Figure 1

.Lightning protection and grounding of a solar power plant in the Krasnodar Kray

Условные обозначения - Legend
- молниеприемник-мачта высотой 10 м - 10 m lightning rod
- полоса стальная оцинкованная сечением 30х4 мм - steel zinc-plated bar with cross-section 30 x 4 mm
- зажим для подключения проводника - clamp for connecting conductor
- вертикальный заземлитель длиной 3 м - 3 m vertical grounding electrode
- зона защиты на высоте 2 м - protection zone at the height 2 m

Figure 1. Equipment layout.

 

The list of necessary materials is given in Table 1.

 

Table 1. List of needed materials.

Part number Name Quantity, pcs. Unit weight, kg Note
LIGHTNING PROTECTION:
1. ZZ-201-010 ZANDZ 10 m vertical lightning arrester (zinc-plated steel; with parts embedded under the foundation) 1    
GROUNDING ARRANGEMENT:
2. GL-11075-50 GALMAR Copper-plated strip (30 * 4 mm / S 120 mm²; 50-meter strip bundle) 26 0,98 Вес за метр
3. ZZ-001-065 ZANDZ Copper-plated threaded grounding rod (D14; 1,5 m) 22 2,00  
4. ZZ-002-061 ZANDZ Threaded coupling 12 0,08  
5. ZZ-003-061 ZANDZ Termination 11 0,07  
6. ZZ-004-060 ZANDZ Guide head for jackhammer attachment 5 0,09  
7. ZZ-005-064 ZANDZ Conductor connection terminal (up to 40 mm) 106 0,312  
8. ZZ-006-000 ZANDZ Conductive grease 2 0,10  
9. ZZ-007-030 ZANDZ Waterproofing tape 36 0,40  
10. ZZ-008-000 ZANDZ Attachment to the hammer (SDS max) 1 0,50  