Lightning Protection for the Cat Unit

ZANDZ Technical Center has received a request to calculate the lightning protection system for the animal shelter. One of the facility was a cat unit. We will consider the example calculation.

Lightning protection for the cat unit

Initial data:

  • soil resistivity 100 Ohm*m;

  • facility dimensions: 17.2 х 18 х 5.88 m.

 

Task:

  • calculate the lightning protection system;

  • calculate the grounding arrangement.

 

Solution:

Lightning protection and grounding of the building are made in accordance with:

 

The facility is “conventional” from the viewpoint of SO and refers to category III of the lightning protection according to RD.

 

A set of measures to meet the necessary requirements to the lightning protection system and to the grounding arrangement of the cat unit includes the following solutions:

1. The facility lightning protection is performed using the lightning grid made of a steel copper-plated wire d8 mm. Grid step is at least 10 m.

2. Metal caps should be provided on all air shafts that will function as natural lightning arresters.

3. A steel copper-plated wire d8 mm (GL-11075) is used as a lightning arrester.

4. Current collectors are connected by horizontal bands near the ground and each 20 m along the building's height according to SO 153-34.21.122-2003, item 3.2.2.3.

5. Installation of current collectors is performed using clamps GL-11747A on the roof, using GL-11703A on ramparts and vertical surfaces. The clamp installation interval is 0.8 to 1.0 m.

6. The multifunctional GL 11551A clamp is used to connect the rolled products over the length and in assemblies.

7. All metal elements located on the roof must be connected to the down conductor using GL-11545A clamps. Stairs, railings, are attached using the GL 11514N ring clamp

8. Galvanized steel electrodes 3 m long in the places of main conductors downdrops are used as vertical ground electrodes. The copper-plated steel strip with a cross-section of 30 x 4 mm, combining all vertical electrodes, is used as a horizontal ground electrode. The distance to the facility foundation is at least 1 m. Strip deepening is 0.5 to 0.7 m.

9. According to EIC-7 issue, item 1.7.55, Grounding devices for protective grounding of electrical installations for buildings and structures and the 2nd and 3rd categories lightning protection of these buildings and structures usually should be common.

10. The design resistance of the grounding arrangement is 2.75 ohms.

11. If there are reinforced concrete structures, they should be connected to current collectors/grounding device.

12. Connection to current collectors is performed with the interval not more than 20-25 m using clamps ZZ-005-064.

 

Ground terminal resistance calculation:

Vertical electrode resistance:

Расчет вертикального заземлителя

where    ρρeq is soil equivalent resistivity, 100 ohm·m;

L – is vertical electrode length, 3 m;

d – is diameter of the vertical electrode, 0.014 m;

– deepening - is the distance from the ground surface to the ground electrode, 2 m;

Расчет заглубления

where     t  – is deepening of the top of the electrode, 0.5 m

 

Horizontal electrode resistance:

Расчет горизонтального заземлителя

where    ρ – is soil resistivity, 100 ohm·m;

b - is horizontal electrode width, 0.03 m;

h - is horizontal electrode depth, 0.7 m;

Lhor – is horizontal electrode length, 78 m.

 

Electrical impedance of the grounding arrangement:

Electrical impedance of the grounding arrangement

where n is number of sets, vertical grounding arrangements 4 pcs, horizontal grounding arrangement 1 pc;

Kutil – is utilization rate, 0.75.

The design resistance of the grounding arrangement is 2,75 ohm..

Diagram of lightning protection and grounding equipment for the cat housing unit

Figure 1. Equipment layout.

 

The list of necessary materials is given in Table 1.

 

Table 1. List of needed materials.

Part number

Name

Quantity, pcs.

Unit weight, kg

Note

LIGHTNING PROTECTION:

1.

GL-11149-50

Copper-plated wire GALMAR (D 8 mm / S 50 mm²; 50-meter coil)

3

0,41

In meters

2.

GL-11545A

GALMAR Main conductor rain water gutter terminal (painted galvanized steel)

4

0,112

 

3.

GL-11551A

GALMAR Clamp for connecting current collectors (painted galvanized steel)

25

0,07

 

4.

GL-11747A

GALMAR Roof clamp coated with metal profile, for current collectors (painted galvanized steel)

150

0,02

 

5.

GL-11703A

Conductor front terminal GALMAR providing 15mm elevation of the main conductor over the terminal (painted galvanized steel)

20

0,02

 

6.

GL-11514N

GALMAR Ring clamp on rainwater pipe for current collector

4

0,076

 

GROUNDING ARRANGEMENT:

7.

GL-11075-50

Copper-clad strip GALMAR (30*4 mm / S 120 mm²; 50-meter strip bundle)

2

0,98

In meters

8.

ZZ-001-065

ZANDZ Copper-plated threaded grounding rod (D14; 1,5 m)

8

2,00

 

9.

ZZ-002-061

ZANDZ Threaded coupling

5

0,08

 

10.

ZZ-003-061

ZANDZ Termination

4

0,07

 

11.

ZZ-004-060

ZANDZ guide head for jackhammer attachment

2

0,09

 

12.

ZZ-005-064

ZANDZ Conductor connection terminal (up to 40 mm)

11

0,312

 

13.

ZZ-006-000

ZANDZ conductive grease

1

0,15

 

14.

ZZ-007-030

ZANDZ Waterproofing tape

4

0,40

 

15.

ZZ-008-000

ZANDZ Attachment to the hammer (SDS max)

1

0,50

 