Lightning Protection of a Field in Kursk

Lightning protection of the field in Kursk

Fields are used for growing various grain crops. The ZANDZ Technical Center received a request to calculate the lightning protection system for a field in Kursk. Normally, the lightning protection is not used in fields, but in this case, the customer asked to protect the 100 x 100 m field containing straw, according to Category I. Let us continue with more detailed review of our offered solution.

Calculation of lightning protection of a field in Kursk

Facility: a field in Kursk

Figure 1. Facility plan.

Figure 1. Facility plan.

Task: to perform calculations for the lighting protection system in Kursk

Solutions to meet the requirements to the lightning protection system of the field in Kursk:

  1. The lightning protection is made in accordance with the Electrical Installations Code (EIC), Rev. 7, SO 153-34.21.122-2003 "Guidelines for the lightning protection of buildings, structures and industrial infrastructure" (hereinafter referred to as SO) and RD 34.21.122-87 "Guidelines for the lightning protection of buildings and structures" (hereinafter referred to as the RD).
  2. The lightning protection of the facility according to Category I is required as per regulatory documents, with reliability of 0.99.
  3. The facility's lightning protection is made using six wire lightning masts of 21 m high (ZZ-204-115), wire installation height is 20 m.
  4. For each lighting arrester, a grounding arrangement is installed as follows:
  • Laying the horizontal grounding device for the current flowing in two directions. Length of each ground electrode is 5 m. The ground electrode is made of a corrosion-resistant steel copper-plated strip with a cross-section of 4 x 30 mm (GL-11075); the laying depth is 0.5 m.
  • At the end of the horizontal ground electrode, one vertical electrode with the length of 3 m is installed in each direction.
  • Vertical and horizontal electrodes, as well as horizontal electrodes with the interception rod are connected using clamps ZZ-005-064.

Results of the calculation performed using the software developed by the Krzhizhanovsky Energy Institute (OAO ENIN):
lightning discharge density into the ground is 4 strikes/square km per year.
Total number of strikes into the system is 0.19 (once per 5 years).
Total number of blowouts is 0.00095 (once per 1,053 years).
The probability of blowouts into the system's facilities is 0.00511.
System reliability is 0,9949.

На рисунке 2 показано расположение оборудования.
В таблице 1 приведен перечень необходимого оборудования и материалов.

Figure 2 shows hardware layout.

Условные обозначения - Legend
Тросовый молниеприемник-мачта высотой 21 м (ZZ-204-120) - Wire lightning mast of 21 m high (ZZ-204-120)
Трос грозозащитный стальной оцинкованный (ZZ-204-001) - Ground wire steel zinc-plated (ZZ-204-001)
Полоса стальная омедненная сечением 30х4 мм (GL-11075) - Steel copper-plated strip with cross-section of 30 x 4 mm (GL-11075)
Зажим для подключения проводника (ZZ-005-064) - Wire clamp (ZZ-005-064)
Вертикальный заземлитель длиной 3 м - Vertical ground electrode of 3 m long

Figure 2 shows hardware layout.

Table 1 includes the list of required hardware and materials.

Position

Designation

Description

Quant.

1.       

ZZ-204-120

ZANDZ support for wire lightning protection system with one cable anchor (suspension height is 20 m)

6

2.       

ZZ-204-001

ZANDZ Ground wire, steel zinc-plated (50 mm2)

375

3.       

GL-11075-50

GALMAR Copper-clad strip (30*4 mm/ S 120 mm²; 50-meter strip bundle)

1

4.       

GL-11075-20

GALMAR Copper-plated strip (30*4 mm/ S 120 mm²; 20-meter strip bundle)

1

5.       

GL-11075-10

GALMAR Copper-clad strip (30x4 mm/S 120 mm²; 10-meter strip bundle)

1

6.       

ZZ-001-065

ZANDZ Copper-plated threaded grounding rod (D14; 1.5 m)

24

7.       

ZZ-002-061

ZANDZ Threaded coupling

13

8.       

ZZ-003-061

ZANDZ Termination

12

9.       

ZZ-004-060

ZANDZ Guide head for jackhammer attachment

5

10.   

ZZ-005-064

ZANDZ Conductor connection terminal (up to 40 mm)

26

11.   

ZZ-006-000

ZANDZ Conductive grease

2

12.   

ZZ-007-030

ZANDZ Waterproofing tape

7

13.   

ZZ-008-000

ZANDZ Attachment to the hammer (SDS max)

1

Do you have any questions about lightning protection of the field or other facilities? Please, contact the ZANDZ Technical Center!