Implementing lightning protection of a sea port in Krasnodar region

Thunderstorm activity in the Southern seaboard regions is much higher than in the major part of the country, that is why implementation of lightning protection for new build construction projects is very relevant.

 

The ZANDZ Technical Center  received a request for the development of lightning protection system for a sea port. Below we will study the solution we prepared.

 

The arrangements were fulfilled in compliance with:

 

The object refers to the III category of lightning protection. System reliability must be not less than 0,9.

 

The set of measures to provide the required lightning protection of a sea port is offered by the following solutions:

  1. lightning protection of the object is carried out with the help of ridge lightning rods (GL-11521SS), which are fixed with the help of holders GL-11525 and air terminal mast 7 m high (ZZ-201-007-3), which is fixed with the help of holders from the lightning rod kit.

  2. steel copper-bonded wire d8 mm (GL-11149) is used as a down conductor.

  3. installation of down conductors is carried out with the help of GL-11747A clamp on the roof, GL-11703A - on vertical surfaces. Distance between the clamps- from 0.8 up to 1.0 meter.

  4. a universal clamp GL-11551A is used for connecting the mill products along the length and in the nods.

  5. All metal elements placed on the roof must be connected to down conductor with the help of clamps GL-11545А. Stairs, handrails are connected with the help of GL-11514N clamp.|

  6. connection of lighting protection system is done to the existing system of down conductors and grounding.

  7. in accordance with the EIC-7 ed., P.1.7.55 - Grounding devices for protective grounding of electrical installations of buildings and structures and lightning protection of the 2nd and 3rd categories of these buildings and structures, as a rule, should be common.

 

Results of the calculation carried out with the software developed by the JSC "Energy Institute to the name of G.M. Krzhizhanovsky (JSC "ENIN"):

The density of lightning strikes into the ground - 4 strikes / sq. km per year;

The total number of strikes into the system in: 0.059 (once in 17 years);

The total number of breakthroughs (strikes directly into the object by-passing lightning rods) - 0.0053 (once in 189 years);

System reliability - 0.911.

 

Location of equipment and protection zone are shown in figure 1.

Молниезащита морского порта

план кровли roofing plan
конек кровли roofing ridge
условные обозначения Type Codes
молниеприемник-мачта высотой 7 м air terminal mast 7 m high
молниеприемник коньковый высотой 2 м ridgy lightning rod 2 m high
проволока стальная омедненная диаметром 8 мм copper bonded steel wire 8 mm in diameter
полоса стальная оцинкованная сечением 40* 4 galvanized steel tape with the cross-section of 40*4 mm
фальцевая клемма для крепления к металлическим конструкциям folding termination for fixation to metal structures
универсальный зажим-соединитель для проволоки universal connector terminal for wire
опуск токоотвода down conductor downdrop

Figure 1 - Location of equipment.

 

The list of equipment and required materials is given in Table 1.

 

Table 1 - Materials requirement list.

№ Product item Name Quantity, pcs. Weight, kg. Note
1. ZZ-201-007-3 ZANDZ Vertical air-terminal mast 7 m high with a set of 2 fastenings to the wall (stainless steel) 1    
2. ZZ-202-002 ZANDZ Clamp to the lightning rod D42 mm for down conductors (stainless steel) 1 0,43  
3. GL-11521SS GALMAR lightning rod 2 meters high for installation in threaded holders (M16; stainless steel) 2 10  
4. GL-11525 GALMAR Ridge holder for lightning rod (thread M16; connection of d10 mm down conductor; bronze) 2    
5. GL-11149-50 GALMAR Copper-bonded wire (D 8mm / S 50 mm²; coil of 50 meters) 3 0,41 В метрах
6. GL-11149-20 GALMAR Copper-bonded wire (D 8mm / S 50 mm²; coil 20 meters) 1 0,41 В метрах
7. GL-11545A GALMAR Clamp on the gutter for a down conductor (painted galvanized steel) 10 0,112  
8. GL-11551A GALMAR Clamp for connecting down conductors (painted galvanized steel) 30 0,07  
9. GL-11747A GALMAR Clamp for the roof covered with metal profiles / corrugated sheets, for down conductor (painted galvanized steel) 180 0,05  
10. GL-11703A GALMAR Clamp to the facade for down conductor with its elevation above the clamp to 15 mm (painted galvanized steel) 10 0,02  
11. GL-11514N GALMAR Clamp-bridge on a gutter for down conductor (tinned copper) 5 0,076  

Do you have any questions on grounding and lightning protection of a sea port? Please contact our ZANDZ Technical center!

See also: