Product items:
Lightning rod is a metal construction, directly perceiving the lightning strike, taking it away from structures located in the protection zone.
This page lists ZANDZ freestanding lightning rods of the height from 8 to 14 m:
ZZ-201-008 - 8 metersZZ-201-010 - 10 metersZZ-201-012 - 12 metersZZ-201-014 - 14 meters
The supply package includes:
- base of faceted galvanized steel, 6, 8, 10 or 12 meters high;
- spike lightning rod of galvanized steel, 2 meters high;
- fasteners for fixing the lightning rod on the support;
- Embedded elements under the foundation.
Installation:
- on concrete flanged embedded parts of the foundation;
- foundation parameters are determined by the calculation and depend on the area of operation of supports and soil parameters;
Bottom design:
The support shank is made of a steel sheet 3-4mm thick, eight-sided, tapered, of different heights from 6.0 to 12 m. The support shank has a flange in the bottom part for fixation to the foundation. In the bottom part of the support there is a hatch that provides access to the place of the grounding device connection. The hatch is closed with a cover, excluding insertion of precipitation and unauthorized entry.
| Total height: | 8000 mm (8 m) | 10000 mm (10 m) |
| Base height (H): | 6000 mm (6 m) | 8000 mm (8 m) |
| Height of the lightning rod part (L): | 2000 mm (2 m) | 2000 mm (2 m) |
| Thickness of the lightning rod wall: | 3-4 mm | 3-4 mm |
| Flange size K: | 280х280 mm | 280х280 mm |
| Distance K1: | 200 mm | 200 mm |
| Diameter of the holes d: | 22 mm | 25,5 mm |
| Weight: | 70 kg | 90 kg |
| Total height: | 12000 mm (12 m) | 14000 mm (14 m) |
| Height of the mast base (H): | 10000 mm (10 m) | 12000 mm (12 m) |
| Height of the lightning rod part (L): | 2000 mm (2 m) | 2000 mm (2 m) |
| Thickness of the lightning rod wall: | 3-4 mm | 3-4 mm |
| Flange size K: | 280х280 mm | 310х310 mm |
| Distance K1: | 200 mm | 250 mm |
| Diameter of the holes d: | 26 mm | 26 mm |
| Weight: | 133 kg | 173 kg |
Prices:
ZZ-201-008 - 47 730,00 rbl. (upon request)
ZZ-201-010 - 66 720,00 rbl. (upon request)
ZZ-201-012 - 84 650,00 rbl. (upon request)
ZZ-201-014 - 93 200,00 rbl. (upon request)


Преимущества:
- производство - РФ;
- длительный срок эксплуатации;
- эстетичный внешний вид;
- высокая антикоррозионная стойкость покрытия (покрытие нанесено методом горячего цинкования по ГОСТ 9.307-89);
- мачта снабжена лючком для подключения заземляющего устройства;
- отсутствие растяжек;
- простота монтажа и установки мачты;
- в комплект поставки входят закладные под фундамент и все необходимые крепежные элементы.