Task:
Facility: Grounding of a balanced TCT type transformer located in a production building.
Soil at the site: sand clay.
Soil resistivity: 100 Ohm/m.
According to item 1.7.101 of the EIC, the resistance of the grounding arrangement to which neutral wires of generators or transformers of single-phase current source terminals are attached, in any season of the year, should be not more than 2, 4, or 8 Ohm, respectively, with the linear voltage 660, 380, and 220 V of a three-phase current source.
In this option, the linear voltage is 380 V; therefore, the resistance of the grounding arrangement should not be more than 4 Ohm.
Solution:
The grounding arrangement consists of three vertical electrodes (copper-plated threaded rods D14; 1.5 m ZZ-001-065 - 2 pcs per 1 electrode), which are interconnected by a copper-plated bar 30 x 4 GL-11074 laid in a trench at least 0.5 m deep from the ground surface and attached to the "ground" terminal of the transformer using a copper-plated bar 30 x 4 GL-11075.
Calculation of resistance of the grounding arrangement:
Vertical electrode (single) resistance:
where:
ρ = 100 Ohm·m is soil resistivity;
L = 6 m is vertical electrode length;
d = 0.014 m is vertical electrode diameter;
T is deepening, i.e. the distance from the ground surface to the grounding arrangement, m:
Ом - Ohm
where t = 0.5 m is the electrode top deepening.
м - m
Horizontal electrode resistance:
Ом - Ohm
where:
ρ = 100 Ohm·m is soil resistivity;
b = 0.03 m is horizontal electrode bar width;
h = 0.5 m is horizontal electrode depth;
Lгор = 20 m is a total length of the horizontal electrode.
Ом - Ohm
Electrical impedance of the grounding arrangement:
where:
n is set amount;
kutil hr = 0.75 is utilization ratio.
Calculated resistance of the grounding arrangement is 3.47 Ohm, which is less than the required value of 4 Ohm.
List of required materials:
№ | Image | Part number | Name | Amount | Unit weight, kg |
1 | ![]() |
ZZ-001-065 | ZANDZ Copper-plated threaded grounding rod (D14; 1,5 m) | 20 | 1,9 |
2 | ![]() |
ZZ-002-061 | ZANDZ Threaded coupling | 16 | 0,08 |
3 | ![]() |
ZZ-002-061 | ZANDZ Termination | 5 | 0,07 |
4 | ![]() |
ZZ-004-060 | ZANDZ Guide head for jackhammer attachment | 4 | 0,09 |
5 | ![]() |
ZZ-005-064 | ZANDZ Conductor connection terminal (up to 40 mm) | 5 | 0,31 |
6 | ![]() |
ZZ-006-000 | ZANDZ Conductive grease | 2 | 0,19 |
7 | ![]() |
ZZ-007-030 | ZANDZ Waterproofing tape | 2 | 0,442 |
8 | ![]() |
ZZ-008-000 | ZANDZ Attachment to the hammer (SDS max) | 1 | 0,48 |
9 | ![]() |
GL-11404 | GALMAR Inspection pit | 5 | 2,6 |
10 | ![]() |
GL-11075 | GALMAR Copper-plated steel strip 30 х 4 mm | 30 (meters) | 0,98 |
Appendix: design in DWG and PDF formats
![]() |
![]() |
![]() |
Согласовано - Approved by
Взам. Инв. № - Repl. Inv. No.
Подп. И дата - Sign. and date
Инв. № подл. - Orig. Inv. No.
Изм. - Rev.
Кол. Уч. - Mod. Q-ty
Лист - Sheet
№ док. - Doc. No.
Подп. - Sign.
Дата - Date
Разраб. - Developed by
ТЦ ZANDZ - ZANDZ TC
Проверил - Checked by
Н. контр. - QC
Заземление симметрирующего трансформатора - Grounding of a balanced transformer
Стадия - Stage
Лист - Sheet
Листов - Sheets
1,5 м - 1.5 m
5 м - 5 m
Зажим для подключения проводника ZANDZ ZZ-005-064 - ZANDZ Conductor connecting clamp ZZ-005-064
GALMAR Колодец контрольный GL-11404 - GALMAR Inspection well GL-11404
Сварное соединение контура заземления с заземляющим проводником - Welded connection between grounding circuit and grounding wire
Заземляющий проводник полоса омедненная 30х4 (GL-1107) - Grounding wire, copper-plated strip 30 x 4 (GL-1107)
Штырь заземления омедненный резьбовой D14, 1.5 м (ZZ-001-065) – 4 шт. - Threaded copper-plated grounding rod D14, 1.5 m (ZZ-001-065), 4 pcs
Муфта соединительная резьбовая ZANDZ ZZ-002-061 - ZANDZ Threaded coupling ZZ-002-061
ВОЙТИ/ЗАРЕГИСТРИРОВАТЬСЯ - LOG IN / REGISTER
Need a design for grounding and lightning protection? Order now by contacting the ZANDZ Technical Center
You may be interested in:
- Useful materials for designers: articles, recommendations, examples
- Free educational webinars with the leading industry experts
- Formulas for calculation of grounding arrangement
- Real-life examples for calculation of the grounding and lightning protection
- Solution examples for grounding and lightning protection of large facilities
Related Articles:







